An overview of 18th Edition Amendment 2

Read our overview of 18th Edition Amendment 2 to understand the latest changes to the Wiring Regulations.


  • Introduction

     

    BS 7671:2018 Amendment 2 was issued 28th March 2022.

    The Wiring Regulations (BS 7671) regularly come under review to ensure all standards are compliant with today’s electrical needs.

     

    These reviews may also happen when standards change at an International or European level to ensure technical consistency with the UK. The general structure of the Wiring Regulations remains unchanged, however, there is now an additional Part 8 on the topic of Functional Requirements of Prosumer’s Electrical Installations. This edition may be implemented immediately however BS 7671:2018+A1:2020 remains current until it is withdrawn on 27th September 2022. During this transition period, a designer or installer can use either edition for compliance for their installation. They will, however, have to choose which edition they are working to, as it is not acceptable to mix clauses from the two amendments. Introducing 18th Edition Amendment 2.

     

    Previously, there was the term ‘installations designed after a certain date are to comply to the new edition’.

     

    This time, Amendment 1 is withdrawn on 27th September 2022 to bring BS 7671 into line with other British Standards when they are reviewed.

     

    Note 1: Completion of an electrical installation designed to the withdrawn standard can be subject to the contractual agreement between all parties involved. Existing installations that have been installed in accordance with earlier editions of the Regulations may not fully comply with Amendment 2 requirements. This does not necessarily mean that they are unsafe for continued use or require upgrading. However, work carried out on an existing installation will need to meet the requirements of Amendment 2 after 27th September 2022.

     

     

  • RCD protection of socket outlets

     

    Regulation 411.3.3 referring to RCD protection of socket-outlets up to 32 A has been redrafted and now has three indents for the requirements of RCD protection not exceeding 30 mA.

    (i) Socket-outlets with a rated current not exceeding 32 A in locations where they are liable to be used by persons of capability BA1, BA3 or children (BA2, BA3),

     

    (ii) Socket-outlets with a rated current not exceeding 32 A in other locations, and

     

    (iii) Mobile equipment with a rated current not exceeding 32 A for use outdoors

     

     

    An explanation of BA1, BA2 and BA3 can be found in Appendix 5 but are summarised as follows:

     

    BA1 Ordinary Person as defined in Part 2 i.e. not skilled or instructed

     

    BA2 Children BA3 Disabled persons i.e. Persons not in command of all their physical and/or intellectual abilities (sick persons, old persons)

     

    There is still an exception to omit RCD protection where a documented risk assessment is carried out. However this can only be applied for indent (ii) and not for (i) or (iii).

     

     

  • Arc Fault Detection Devices

     

    Probably the biggest change to be aware of in Amendment 2, is that the use of Arc Fault Detection Devices (AFDD) have changed from being recommended to a mandatory use in certain types of installations.

     

    With the increase of new technologies being introduced and more widely used, these devices are becoming more vitality important to provide additional protection against fire.

     

    Regulation 421.1.7 now states AFDD conforming to BS EN 62606 shall be provided for single-phase AC final circuits supplying socket-outlets with a rated current not exceeding 32 A in:

     

    - Higher Risk Residential Buildings (HRRB)

    - Houses in Multiple Occupation (HMO)

    - Purpose-Built Student Accommodation (PBSA)

    - Care homes

     

    For all other premises, the use of AFDDs is recommended for single-phase AC final circuits supplying socket-outlets not exceeding 32 A.

     

    Higher Risk Residential Buildings (HRRB)

    Higher Risk Residential Buildings are assumed to be residential buildings over 18 m in height or in excess of six storeys, whichever is met first. Should this building incorporate a business premises on the ground floor for example then this too could fall under this requirement.

     

    Houses in Multiple Occupation (HMO)

    A house in multiple occupation is a property rented out by at least three people who are not from one “Household” but share facilities like a bathroom or kitchen.

     

    Purpose-Built Student Accommodation

    PBSA is housing built specifically for students to live in.

    Care home

    A care home is a place where personal care and accommodation are provided together.

     

     

  • Precautions where particular risk of fire exists

     

    A new definition has been included in Amendment 2 of protected escape route. This is defined as: A route enclosed with specified fire-resisting construction designated for escape to a place of safety in the event of an emergency.

     

    Regulation 422.2 requires that: Cables or other electrical equipment shall not be installed in a protected escape route unless part of:

     

    (i) an essential fire safety or related safety system

    (ii) general needs lighting

    (iii) socket-outlets provided for cleaning or maintenance

     

    There are also requirements for the types of cables and cable management systems to be used in this specific area which are fire resistant or installed within non-flame propagating cable management systems.

     

     

  • Surge Protection Devices

     

    Regulation 443.4.1 now requires protection against transient overvoltages to be provided where the consequence caused by the overvoltage could result in:

     

    (i) serious injury to, or loss of, human life

    (ii) failure of a safety service, as defined in Part 2

    (iii) significant financial or data loss

     

    For all other cases, protection against transient overvoltages shall be provided, unless the owner of the installation declares it is not required due to any loss or damage being tolerable and they accept the risk of damage to equipment and any consequential loss.

     

    Indent (ii) however requires the use of overvoltage protection devices to protect a Safety Service. This is defined in Part 2 as; “An electrical system for electrical equipment provided to protect or warn persons in the event of a hazard, or essential to their evacuation from a location.”

     

    A fire or smoke detection system would fall into this definition. If this system is supplied from the electrical installation then an overvoltage could cause it to fail and, as such, requires protection. The simplest way to provide this protection may be to supply it at the distribution board or consumer unit.

     

    The requirements of Section 443 on protection against transient overvoltages has been completely rewritten with the risk assessment removed.

     

     

  • Selection of RCDs

     

    Different types of RCDs were introduced when the 18th Edition was first published in 2018 with Regulation 531.3. Amendment 2 has gone further saying that Type AC RCDs shall only be used where it is known the load current contains no DC components. This will only be in a purely resistive item of equipment such as a resistive heating element or filament lighting. It is likely then that Type A RCDs as a minimum will generally be used.

     

    Unwanted tripping

     

    This is still a consideration for the designer of the installation with Regulation 531.3.2. To achieve this, they should ideally ensure there is no more than 30% of the rated residual operating current due to protective conductor current and/or earth leakage currents (i.e. 9mA for a 30mA device). There is a new indent (ii) to consider the use of RCBOs as opposed to split load arrangements for this purpose.

     

    Type AC

    General purpose use RCD can detect & respond to AC sinusoidal wave only

     

    Type A

    Equipment incorporating electronic components RCD can detect & respond as for Type AC, PLUS pulsating DC components

     

    Type F

    Equipment with frequency controlled speed drives RCD can detect & respond as for Type A, PLUS high-frequency residual current

     

    Type B

    Electric vehicle chargers, PV supplies RCD can detect & respond as for Type F, PLUS smooth DC residual current

     

     

     

  • Identification and notices

     

    It is not uncommon now for consumer units in particular to be in a location visible to a user/ homeowner. BS 7671 requires warning and/or instruction labels to be fitted at or near this distribution board for the information of the installation owner. Such labels usually have been in the form of stickers attached to the enclosure and are required for RCD test information, periodic inspection intervals among others.

     

    Amendment 2 states that the requirements of this regulation now need not be applied for domestic or similar installations where certification for initial verification, complete with guidance for recipients, has been issued to the person ordering the work. This guidance for recipients must contain all the information previously contained on the sticker or label. This applies to the RCD test label, periodic test label, presence of SPD label (new requirement). The only exception is the warning notice of additional supplies which, if required, will still need to be present on the enclosure.

     

     

  • Generating set operating in parallel

     

    Solar photovoltaic (PV) installations are covered by Section 712 which has been extensively revised and expanded.

     

    Connected with this subject is Section 551 Low Voltage Generator Sets. As a PV system is a generating set usually operating in parallel with the normal electrical supply, Regulation 551.7 refers.

     

    A new requirement is for the current rating of low voltage switchgear assembly to be suitably rated, considering the additional supply from this generating set.

     

    The assembly shall be selected such that: InA ≥ In + Ig(s)

     

    Where

    - InA is rated current of the assembly

    - In is rated current of incoming protective device (e.g. 100 A)

    - Ig(s) is rated current of generating set (e.g. 16 A)

    Consumer units will generally not have a current rating InA of 116 A. Manufacturers instructions will need to be followed to ensure a compliant installation.

     

    One solution could be to provide an overcurrent protective device within (or external to) the consumer unit, thus limiting the current through the assembly. The assembly will need to be certified by the manufacturer to the relevant part of the BS EN 61439 series and a declaration of conformity to this standard should be provided if requested.

     

     

  • Inspection & testing

     

    Insulation Resistance

    Chapter 64 to do with initial verification has undergone some changes.

     

    Regulation group 643.3 covering insulation resistance explains that, where equipment in the installation could influence the result of the test or be damaged, it should be disconnected in order to carry out this insulation resistance test.

     

    However following the reconnection of such equipment, a test at 250 V DC shall be carried out between live conductors and the protective conductor, which should be connected to the earthing arrangement. The result of this test shall be at least 1 MΩ.

     

    There may be some equipment however that would show false readings at this test. It is therefore important that manufacturer’s instructions be consulted and if necessary the equipment disconnected during this 250 V DC test.

     

    RCD testing

     

    The testing of RCDs has become more complex with the introduction of various different types of RCD. All RCDs, regardless of type, can detect and respond to an AC waveform. To simplify the testing procedure it is only now a requirement for verification purposes to carry out the AC test that is common to all types. So regardless of RCD type, the effectiveness is deemed to have been verified by testing the device using an AC waveform at a test current of 1 x IΔn.

     

    The disconnection time shall be;

    - 300 ms maximum for general non-delayed type

    - For delayed or ‘S’ type devices between 130 ms minimum and 500 ms maximum

     

     

     

  • Electrical vehicle charging installations

    Section 722 Electric vehicle charging installations was the subject of BS 7671:2018+A1:2020. This has been incorporated into Amendment 2 along with some minor changes.

     

    More details on this subject can be found in the Hager Bitesize guide to electric vehicles.