Technical characteristics
Electric current
-
Rated current125 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-240 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-285 kA
-
Rated current 10°C according to IEC 60947155.30 A
-
Rated current 15°C according to IEC 60947151.80 A
-
Rated current 20°C according to IEC 60947148.30 A
-
Rated current 25°C according to IEC 60947144.60 A
-
Rated current 30°C according to IEC 60947141 A
-
Rated current at 35°C according to IEC 60947137.10 A
-
Rated current at 40°C according to IEC 60947133.10 A
-
Rated current 45°C according to IEC 60947129.10 A
-
Rated current 50°C according to IEC 60947125 A
-
Rated current 55°C according to IEC 60947120.60 A
-
Rated current at 60°C according to IEC 60947116.20 A
-
Rated current 65°C according to IEC 60947111.80 A
-
Rated current 70°C according to IEC 60947107.20 A
Architecture
-
Number of poles3
-
Control/operation elementToggle
-
Device construction typeFixed built-in
Tripping
-
Response time when opening10 ms
Frequency
-
Frequency50 - 60 Hz
Voltage
-
Rated impulse withstand voltage Uimp8,000 V
-
Rated insulation voltage Ui800 V
Functions
-
Trip unitTM F/F
Power
-
Total power loss under IN27.70 W
Endurance
-
Electric endurance in number of cycles10,000
-
Number of mechanical operations20,000
Safety
-
Ingress Protection (IP) classIP4X
Connection
-
Cross-section flexible conductor35 - 150 mm²
-
Cross-section rigid conductor35 - 185 mm²
Settings
-
Thermal protection knob setting xIN1, 1
-
Adjustment range short-term delayed short-circuit release0 - 0 A
Compatibility
-
Suitable for DIN RailNo
Installation, mounting
-
Nominal tightening torque12 - 12 Nm
-
Mounting-/Connection PositionFront
Main electrical attributes
-
Magnetic protection trip time0 - 0 ms
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers Learn More
Certifications and documents
Downloads
-
Product image
-
Product datasheet
Hager Product data sheet HNB125Z
Moulded Case Circuit Breaker x250 3P 40kA 125A TM
PDF -
Installation manual
Installation manual International 2021-06-09
PDF9,54 MB -
Product data sheet
UK_PD_TDS_MCCBx250.pdf
Technical data sheet for MCCB x250.
PDF1,63 MB -
Declaration of conformity
EU Declaration of Conformity
PDF326,09 kB
UKCA Declaration of Conformity
PDF329,43 kB