DIMMER 4 CHANNELS 300W NE WITH PARALLELIZATION TXA664AN
EAN
3250617579872
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Functions
-
Multi-phase modesuitable to switch different external conductors
-
FunctionLearning function for optimised operation of compact fluorescent lamps and LED luminaires can be activated via the bus
-
Soft startupbulb-preserving soft startup
-
Operating modeload coupling of 4 channels to increase output power using parallel connection of the outputs
Configuration
-
Number of modules8
Controls and indicators
-
Indicator lampyes
-
Operationmanual operation also possible without bus, e.g. on building site ; Manual operation can be activated via selection switch, thereby deactivation of the KNX function ; Manual operation per channel via button with integrated status LED, thereby lockout of KNX function
-
Indication / displaystatus LED integrated in the manual operation button
-
Manual selection switches / push-buttonsselection switch for manual/bus operation as well as load setting
-
Button / push-buttonwith illuminated programming button
Main electrical features
-
Frequency50/60 Hz
-
Rated current5200 mA
Voltage
-
Auxiliary voltage230 V AC
-
Input voltage230 V AC
-
Operating voltage over bus21…32 V DC
-
System supply voltage30V DC via bus
Electric current
-
Bus current consumption (data transfer)< 2.4 mA
Fuse
-
Fuseshort-circuit and overload proof (electronic fuse) ; short-circuit proof and overload proof (display using LEDs) ; overheating protection (display using LEDs)
Dimensions
-
Width of rail mounted device (RMD)8 modules
Power
-
Dimmable conventional transformersper channel 300 VA
-
Incandescent bulb power5 / 300 W
-
Total power loss under IN0.35 W
-
Power dissipation per coil1 W
-
Power of the variator5 / 300 W
-
Electronic transformersper channel 300 W
Power supply
-
Supply voltage230 V +10% / -15%
Fluorescent bulbs control
-
Quantity energy-saving lampsper channel max. 8
-
Dimmable energy-saving lampsper channel 60 W
-
Power lighting fluo lamps60W
LED control
-
Quantity of dimmable, 230 V retrofit LED lampsper channel max. 8
-
Max number of LED/CFL lamps8
-
Dimmable LED lampsper channel 60 W
-
Power LED60 W
-
LEDStatus LED integrated in manual operation button ; Overheating protection, display using LEDs ; Overload protection, display via LED
Incandescent bulbs control
-
Max. power with incandescent lamps300 W
-
230 V incandescent lamps and halogen lampsper channel 300 W
Connection
-
Connection cross-sect. flexible conductor0,75 / 2,5mm²
-
Connection cross-sect. rigid cable0,75 / 2.5mm²
-
Type of loaduniversal
-
Conductor cross-section (flexible)0.75…2.5 mm²
-
Conductor cross-section (rigid)0.75…2.5 mm²
-
Bus coupling unitwith integral bus coupling unit
-
Type of connectionwith QuickConnect plug-in terminals
-
Bus connectionbus connection via connecting terminal
-
Type of connectionquick connect
Settings
-
Supported configuration modeseasy, system
-
Parameterisationpreset behaviour in the event of bus voltage failure/return
Scope of delivery
-
Bus connection includedYes
Equipment
-
Number of outputs4
-
Type of dimmerdimming actuator
-
Substation inputNo
-
Power boost suitableNo
-
Modular expandabilityNo
-
Dimming principlephase cut-on or cut-off according to load type, self-learning ; minimum/maximum dimming values per channel settable on device
-
low noisevery low noise
Use
-
Local operation/hand operationYes
Safety
-
REACH conformNo
-
RoHS conformYes
-
Halogen freeNo
-
Protectionwith overheating, overload and short-circuit protection
Use conditions
-
Operating temperature-5…45 °C
-
Storage/transport temperature-20…70 °C
Identification
-
Device familyTXA
-
Main design lineKNX
Downloads
-
Product image
-
ProductNotice
Instruction manuals for TXA664AN
PDF3 MB -
Technical information
PDF733 KB -
ProductROHS
Pollutant guidelines for TXA664AN
REACH-declaration 2023-10-20 (english)
PDF33 KBPollutant guidelines for TXA664AN
RoHS-declaration 2023-10-20 (english)
PDF33 KB -
ProductEnvironmentProfile
Product environmental profile for TXA664AN
PDF435 KBProduct environmental profile for TXA664AN
PDF431 KB
More documentation