Service Temporarily Unavailable

The server is temporarily unable to service your request due to maintenance downtime or capacity problems. Please try again later.

MCCB h3 x630 TM 4x400A 25kA • HHJ401DR | Hager

Moulded Case Circuit Breaker h3 x630 TM ADJ 4P4D N0-100% 400A 25kA FTC HHJ401DR

EAN-Nr.
3250613199173
Packaging
1 piece

Complete your system

Optional accessories

  • See more (60)
    • AOB MCCB type A 4 products available
    • Terminal cover 5 products available
    • Motor operator 12 products available
    • Mechanic accessories for low-voltage components 2 products available
    • Operating shaft for power breaker 3 products available
    • Connection Functions 5 products available

    Technical characteristics

    Electric current
    • Rated current
      400 A
    • Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-2
      25 kA
    • Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-2
      35 kA
    • Rated service breaking capacity Ics under 230 V AC according to IEC 60947-2
      35 kA
    • Rated service breaking capacity Ics under 400 V AC according to IEC 60947-2
      25 kA
    • Rated current 10°C according to IEC 60947
      470.70 A
    • Rated current 15°C according to IEC 60947
      462.50 A
    • Rated current 20°C according to IEC 60947
      454.10 A
    • Rated current 25°C according to IEC 60947
      445.50 A
    • Rated current 30°C according to IEC 60947
      436.80 A
    • Rated current at 35°C according to IEC 60947
      427.90 A
    • Rated current at 40°C according to IEC 60947
      418.80 A
    • Rated current 45°C according to IEC 60947
      409.50 A
    • Rated current 50°C according to IEC 60947
      400 A
    • Rated current 55°C according to IEC 60947
      390.30 A
    • Rated current at 60°C according to IEC 60947
      380.30 A
    • Rated current 65°C according to IEC 60947
      370 A
    • Rated current 70°C according to IEC 60947
      359.40 A
    Architecture
    • Number of poles
      4
    • Control/operation element
      Toggle
    • Device construction type
      Fixed built-in
    • Neutral position
      Left
    Tripping
    • Response time when opening
      10 ms
    Frequency
    • Frequency
      50 - 60 Hz
    Voltage
    • Rated impulse withstand voltage Uimp
      8,000 V
    • Rated insulation voltage Ui
      800 V
    • Rated operational voltage Ue
      220 - 415 V
    Functions
    • Trip unit
      TM A/A
    Power
    • Total power loss under IN
      80 W
    Safety
    • Ingress Protection (IP) class
      IP4X
    Settings
    • Thermal protection knob setting xIN
      0.63, 0.8, 1
    Cable
    • Cable material
      Copper
    Compatibility
    • Compatible with RDC AOB
      Yes
    • Suitable for DIN Rail
      No
    • Suitable for distribution board
      Yes
    Dimensions
    • Height
      260 mm
    • Width
      185 mm
    • Depth
      150 mm
    • Downstream busbar: width, height, diameter screw (max.)
      10 mm, 12 mm, 32 mm
    • Top stream busbar: width, height, diameter screw (max.)
      10 mm, 12 mm, 32 mm
    Installation, mounting
    • Mounting-/Connection Position
      Front
    • Nominal tightening torque
      18 - 18 Nm
    • Nominal tightening torque down terminal
      18 - 18 Nm
    • Nominal tightening torque top terminal
      18 - 18 Nm

    Environmental value

    We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More

    RoHS conform Yes
    REACh-SVHC free Yes