Service Temporarily Unavailable

The server is temporarily unable to service your request due to maintenance downtime or capacity problems. Please try again later.

MCCB h3+ P160 TM 3x160A 70kA • HES160DC | Hager
EAN-Nr.
3250613177201
Packaging
1 piece

Moulded Case Circuit Breaker h3+ P160 TM ADJ 3P3D 160A 70kA CTC HES160DC

Complete your system

Optional accessories

  • See more (18)
    • Under voltage coil 3 products available
    • Shunt release 1 products available
    • Auxiliaries contact block 5 products available
    • Connection Functions 4 products available
    • Auxiliaries cable adaptor 1 products available
    • Terminal cover 2 products available

    Technical characteristics

    Electric current
    • Rated current
      160 A
    • Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-2
      70 kA
    • Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-2
      85 kA
    • Rated service breaking capacity Ics under 230 V AC according to IEC 60947-2
      85 kA
    • Rated service breaking capacity Ics under 400 V AC according to IEC 60947-2
      50 kA
    • Rated ultimate short-circuit breaking capacity Icu under 660 V AC IEC 60947-2
      6 kA
    • Rated ultimate short-circuit breaking capacity Icu under 690 V AC IEC 60947-2
      6 kA
    • Rated current 10°C according to IEC 60947
      192.10 A
    • Rated current 15°C according to IEC 60947
      188.40 A
    • Rated current 20°C according to IEC 60947
      184.60 A
    • Rated current 25°C according to IEC 60947
      180.70 A
    • Rated current 30°C according to IEC 60947
      176.80 A
    • Rated current at 35°C according to IEC 60947
      172.70 A
    • Rated current at 40°C according to IEC 60947
      168.60 A
    • Rated current 45°C according to IEC 60947
      164.40 A
    • Rated current 50°C according to IEC 60947
      160 A
    • Rated current 55°C according to IEC 60947
      155.50 A
    • Rated current at 60°C according to IEC 60947
      150.90 A
    • Rated current 65°C according to IEC 60947
      146.20 A
    • Rated current 70°C according to IEC 60947
      141.20 A
    Architecture
    • Number of poles
      3
    • Control/operation element
      Toggle
    • Device construction type
      Fixed built-in
    • Neutral position
      Without neutral
    Frequency
    • Frequency
      50 - 60 Hz
    Voltage
    • Rated impulse withstand voltage Uimp
      8,000 V
    • Rated insulation voltage Ui
      800 V
    • Rated operational voltage Ue
      220 - 690 V
    Functions
    • Trip unit
      TM A/A
    Power
    • Total power loss under IN
      42.30 W
    Endurance
    • Electric endurance in number of cycles
      10,000
    • Number of mechanical operations
      40,000
    Safety
    • Ingress Protection (IP) class
      IP4X
    Connection
    • Cross-section flexible conductor
      6 - 70 mm²
    • Cross-section rigid conductor
      6 - 95 mm²
    Connectivity
    • Type of connection
      Screw terminal
    Cover, door
    • Interlockable
      Yes
    Settings
    • Thermal protection knob setting xIN
      0.63, 0.8, 1
    Cable
    • Cable material
      Copper
    Compatibility
    • Compatible with RDC AOB
      No
    • Suitable for DIN Rail
      No
    • Suitable for distribution board
      Yes
    Dimensions
    • Height
      130 mm
    • Width
      90 mm
    • Depth
      97 mm
    Electrical protection
    • Instantaneous protection (li): dial setting coefficient
      6, 7, 8, 9, 10
    Installation, mounting
    • Mounting-/Connection Position
      Front
    • Nominal tightening torque
      6 - 6 Nm
    • Nominal tightening torque down terminal
      6 - 6 Nm
    • Nominal tightening torque top terminal
      6 - 6 Nm

    Environmental value

    We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More

    RoHS conform Yes
    REACh-SVHC free Yes