MCB 1P 3kA C-25A 1M MW125
EAN
3250614531255
Packaging
12 PCEs
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Number of protected poles1
-
Number of poles1 P
-
Type of pole1 P
-
CurveC
Functions
-
Concurrently switching N-neutralNo
Configuration
-
Number of modules1
Connectivity
-
Top connection alignement for modular devicesAligned terminal
-
Bottom connection alignement for modular devicesAligned terminal
Main electrical features
-
Rated short circuit breaking capacity Icn AC according IEC60898-13 kA
-
Rated operational voltage Ue230 / 400 V
-
Type of supply voltageAC
-
Frequency50/60 Hz
Voltage
-
Rated insulation voltage500 V
-
Rated impulse withstand voltage4000 V
Electric current
-
Rated current25 A
-
Rated service breaking capacity Ics AC according IEC 60898-13 kA
-
min/maxi threshold value of the AC thermal operation1.13 / 1.45 In
-
Magnetic regulating currrent5 / 10 In
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-13 kA
-
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-23 kA
Electric current / temperature
-
Rating current -25°C32.07 A
-
Rating current -20°C31.49 A
-
Rating current -15°C30.91 A
-
Rating current -10°C30.31 A
-
Rating current -5°C29.7 A
-
Rating current 0°C29.07 A
-
Rating current 5°C28.43 A
-
Rating current 10°C27.78 A
-
Rating current 15°C27.11 A
-
Rating current 20°C26.43 A
-
Rating current 25°C25.72 A
-
Rating current 30°C25 A
-
Rating current 35°C24.26 A
-
Rating current 40°C23.49 A
-
Rating current 45°C22.69 A
-
Rating current 50°C21.87 A
-
Rating current 55°C21.01 A
-
Rating current 60°C20.12 A
-
Rating current 65°C19.19 A
-
Rating current 70°C18.21 A
Current correction factors
-
Correction factor of rating current for 2 devices placed side-by-side1
-
Correction factor of rating current for 3 devices placed side-by-side0.95
-
Correction factor of rating current for 4 and 5 devices placed side-by-side0.9
-
Correction factor of rating current for 6 devices placed side-by-side0.85
-
Correction factor of magnetic tripping with 100 Hz1.1
-
Correction factor of magnetic tripping with 200 Hz1.2
-
Correction factor of magnetic tripping with 400 Hz1.5
-
Correction factor of magnetic tripping with 60 Hz1
Dimensions
-
Depth of installed product70 mm
-
Height of installed product83 mm
-
Width of installed product17.5 mm
Frequency
-
Frequency50 to 60 Hz
Power
-
Total power loss under IN3.23 W
-
Power loss per pole at In3.23 W
Endurance
-
Electric endurance in number of cycles4000
-
Number of mechanical operations20000
Installation, mounting
-
Type of top connection for modular deviceswith screw
-
Tightening torque2,8Nm
-
Type of Bottom Connection for modular devicesBIconnect
Connection
-
Connection cross-sect. flexible conductor1 / 25mm²
-
Connection cross-sect. rigid cable1 / 35mm²
-
Connection cross-section of input and output with screws, for massive conductors1 / 35 mm²
-
Connection cross section of access and exit with screws, for flexible conductor1 / 25 mm²
-
Type of connectionwith screw
Standards
-
Standard textEN 60898-1
-
European directive WEEEnot concerned
Use conditions
-
Operating temperature-25…70 °C
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Class of energy limitation I²t3
-
Altitude2000 m
-
Air humidity protectionfor all climates
-
Storage/transport temperature-25…80 °C
Downloads
-
Product image
-
ProductECDeclaration
EU Declaration of conformity for MW125
Declaration
PDF579 KBEU Declaration of conformity for MW125
EU Declaration of Conformity
PDF519 KBEU Declaration of conformity for MW125
Declaration
PDF339 KB -
ProductEnvironmentProfile
Product environmental profile for MW125
PDF241 KBProduct environmental profile for MW125
PEP_Hager_MC116A_EN_13072011
PDF58 KB
More documentation