Change-over switch 4P 630A HI458
EAN
3250613190057
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Type of orderLong thumb-grip
-
Number of poles4 P
-
Type of pole4 P
-
Type of caseFixed built-in
Functions
-
Reversing switchYes
Controls and indicators
-
Motor drive integratedNo
Main electrical features
-
Rated operational voltage Ue380 / 400 / 500 / 690 V
-
Frequency50/60 Hz
Voltage
-
Rated insulation voltage1000 V
-
Rated impulse withstand voltage12000 V
-
Rated operational voltage in DC260 / 400 / 500 V
Electric current
-
Rated operational current in AC21category B630 A
-
Acceptable current rating with AC22 category A630 A
-
Rated current630 A
-
Short-circuit current with gI-gG fuses50 kA
-
Rated short-time withstand current 1s10 kA
-
Thermal rated current outside of housings630 A
-
Rated operational current in AC21 category A630 A
-
Acceptable current rating with AC22 category B630 A
-
Rated operational current in AC23 category A630 A
-
Acceptable current rating with AC23 category B630 A
Power
-
Nominal power under 440/500, 50Hz355 kW
-
Nominal power under 660 V, 50 Hz295 kW
-
Active power under 380/415 V, 50 Hz355 kW
-
Total power loss under IN92.7 W
-
Power loss per pole at In32.4 W
-
Contact rating with 400 V in AC1414 kW
Endurance
-
Electrical durability at nominal load in AC21in operating cycles1000
-
Electrical durability at nominal load in AC22 in operating cycles200
-
Number of mechanical operations5000
Cover, door
-
InterlockableYes
Connection
-
Connection cross-sect. rigid cable2x150 / 2x300mm²
-
Type of connectionTerminal
Equipment
-
Number of auxiliary contacts as normally closed contact0
-
Number of auxiliary contacts as normally open contact0
-
Number of auxiliary contacts as change-over contact0
-
Motor drive optionalNo
Standards
-
Standard textIEC 60947-3
Safety
-
REACH conformYes
-
RoHS conformYes
Use conditions
-
Operating temperature-20…70 °C
-
Air humidity protectionyes according to IEC 68-2-30
-
Storage/transport temperature-40…65 °C
Downloads
-
Product image
-
ProductNotice
Instruction manuals for HI458
Commutateur 4P
PDF235 KB -
ProductECDeclaration
EU Declaration of conformity for HI458
EU Declaration of Conformity
PDF637 KBEU Declaration of conformity for HI458
Declaration
PDF621 KBEU Declaration of conformity for HI458
Deklaracja zgodności UE
PDF333 KBEU Declaration of conformity for HI458
Declaration
PDF573 KB -
ProductROHS
Pollutant guidelines for HI458
REACH 1907/2006 declaration Hager Switzerland
PDF1 MBPollutant guidelines for HI458
RoHS 2011/65/EU declaration Hager Switzerland
PDF1 MBPollutant guidelines for HI458
REACH-declaration 2023-10-20 (english)
PDF32 KBPollutant guidelines for HI458
RoHS-declaration 2023-10-20 (english)
PDF33 KB
More documentation