Load break switch 3P 63A HAC306
EAN
3250613140274
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Number of poles3 P
-
Type of pole3 P
-
Type of caseFixed built-in
Functions
-
Reversing switchNo
Configuration
-
Number of modules3
Controls and indicators
-
Motor drive integratedNo
Main electrical features
-
Rated operational voltage Ue380 / 415 V
-
Frequency50 Hz
Voltage
-
Rated insulation voltage800 V
-
Rated impulse withstand voltage8000 V
Electric current
-
Rated operational current in AC21category B63 A
-
Rated current63 A
-
Short-circuit current with gI-gG fuses50 kA
-
Rated short-time withstand current 1s1.5 kA
-
Acceptable current rating with AC22 category B63 A
-
Rated operational current in AC23 category A63 A
-
Acceptable current rating with AC23 category B63 A
Power
-
Total power loss under IN4.5 W
-
Power loss per pole at In1.5 W
-
Contact rating with 400 V in AC141 kW
Cover, door
-
InterlockableYes
Equipment
-
Number of auxiliary contacts as normally closed contact0
-
Number of auxiliary contacts as normally open contact0
-
Number of auxiliary contacts as change-over contact0
-
Motor drive optionalNo
Standards
-
European directive WEEEconcerned
Safety
-
Protection index IPIP20
Use conditions
-
Operating temperature-20…70 °C
Downloads
-
Product image
-
ProductNotice
Instruction manuals for HAC306
PDF1 MB -
ProductECDeclaration
EU Declaration of conformity for HAC306
Declaration
PDF835 KBEU Declaration of conformity for HAC306
Declaration
PDF634 KB -
ProductROHS
Pollutant guidelines for HAC306
RoHS-declaration 2023-10-20 (english)
PDF33 KBPollutant guidelines for HAC306
REACH-declaration 2023-10-20 (english)
PDF32 KB