Technical properties
Electric current
-
Rated current32 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-215 kA
-
Rated current -25°C39.04 A
-
Rated current at -20°C38.45 A
-
Rated current -15°C37.86 A
-
Rated current -10°C37.25 A
-
Rated current -5°C36.64 A
-
Rated current at 0°C36.01 A
-
Rated current 5°C35.37 A
-
Rated current 10°C34.73 A
-
Rated current 15°C34.06 A
-
Rated current at 20°C33.39 A
-
Rated current 25°C32.70 A
-
Rated current 30°C32 A
-
Rated current 35°C31.26 A
-
Rated current at 40°C30.50 A
-
Rated current at 45°C29.72 A
-
Rated current at 50°C28.92 A
-
Rated current 55°C28.10 A
-
Rated current 60°C27.26 A
-
Rated current 65°C26.38 A
-
Rated current 70°C25.48 A
Architecture
-
Type of pole4P
-
CurveD
Capacity
-
Number of modules4
Installation, mounting
-
Nominal tightening torque top terminal2.80 - 2.80 Nm
-
Nominal tightening torque down terminal2.80 - 2.80 Nm
-
Nominal tightening torque2.80 - 2.80 Nm
-
Type of bottom connection for modular devicesbiconnect
-
Type of top connection for modular devicesScrew terminal
-
360° mounting position possibleYes
Main electrical attributes
-
Rated short-circuit breaking capacity Icn AC according to IEC 60898-110 kA
Voltage
-
Rated operational voltage Ue400 - 400 V
-
Type voltage supplyAC
-
Rated insulation voltage Ui500 V
-
Rated impulse withstand voltage Uimp6000 V
Frequency
-
Frequency50 - 60 Hz
Connection
-
Cross-section of input and output with screws, for massive conductors1 - 35 mm²
-
Cross-section of input and output with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for massive conductors1 - 35 mm²
Safety
-
Ingress Protection (IP) classIP20
-
Grid distance60 mm
Use conditions
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Operating temperature-25 - 70 °C
Power
-
Total power loss under IN16.50 W
Endurance
-
Electric endurance in number of cycles4000
-
Number of mechanical operations20000
Connectivity
-
Type of connectionScrew terminal
-
Top connection alignment for modular devicesAligned terminal
-
Down connection alignment for modular devicesAligned terminal
Dimensions
-
Height83 mm
-
Width70 mm
-
Depth70 mm