Moulded Case Circuit Breaker h3 x630 TM ADJ 4P4D N0-100% 250A 25kA FTC HHJ251DR
EAN-Nr.
3250613199074
Packaging
1 piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical characteristics
Architecture
-
Type of orderToggle
-
Neutral positionleft
-
Number of protected poles4
-
Number of poles4 P
-
Type of pole4P4D N:0/100%
-
Type of caseFixed built-in
Functions
-
Complete device with protection unitYes
-
Version as main switchYes
-
Version as emergency stop installationNo
-
Version as safety switchNo
-
Version as maintenance-/service switchYes
-
Trip UnitTM A/A
-
Integrated earth fault protectionNo
-
Concurrently switching N-neutralYes
Controls and indicators
-
Motor drive integratedNo
Main electrical features
-
Rated operational voltage Ue220 / 415 V
-
Type of supply voltageAC
-
Frequency50/60 Hz
Voltage
-
Rated insulation voltage800 V
-
Rated impulse withstand voltage8 kV
-
With under voltage releaseNo
Electric current
-
Rated current250 A
-
Thermal protection nob setting xIN0.63 / 0.8 / 1
-
Rating current 10°C according to IEC 60947293.3 A
-
Rating current 15°C according to IEC 60947288.2 A
-
Rating current 20°C according to IEC 60947283.1 A
-
Rating current 25°C according to IEC 60947277.8 A
-
Rating current 30°C according to IEC 60947272.5 A
-
Rating current 35°C according to IEC 60947267.1 A
-
Rating current 40°C according to IEC 60947261.5 A
-
Rating current 45°C according to IEC 60947255.8 A
-
Rating current 50°C according to IEC 60947250 A
-
Rating current 55°C according to IEC 60947244.1 A
-
Rating current 60°C according to IEC 60947238 A
-
Rating current 65°C according to IEC 60947231.7 A
-
Rating current 70°C according to IEC 60947225.3 A
-
Breaking capacity on 1 pole for IT 230V NF 60947-210 kA
-
Breaking capacity on 1 pole for IT 400V NF 60947-210 kA
-
Breaking capacity on 1 pole for IT 415V NF 60947-210 kA
-
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-235 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-235 kA
-
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-225 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-225 kA
-
Range of the thermal adjustment160 / 200 / 250 A
-
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-235 kA
-
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-225 kA
Dimensions
-
Depth of installed product150 mm
-
Height of installed product260 mm
-
Width of installed product185 mm
Frequency
-
Frequency50 to 60 Hz
Power
-
Power loss per pole at 0.63*In9.4 W
-
Power loss per pole at 0.8*In15.2 W
-
Total power loss at 0.63*In28.3 W
-
Total power loss at 0.8*In45.7 W
-
Total power loss under IN71.4 W
-
Power loss per pole at In23.8 W
Tripping
-
Time of response when opening10 ms
Installation, mounting
-
Tightening torque18Nm
-
DIN rail mounting with optional adaptatorNo
-
Suitable for front mountingNo
-
Suitable for ground mountingYes
Connection
-
ConnectionFront connection
-
Type of connectionTerminal
Protection
-
Instantaneous protection (Ii): typefixed
Cable
-
Cable MaterialCu
Settings
-
Range of the magnetic adjustment1250 / 1500 / 1750 / 2000 / 2250 / 2500 A
-
Magnetic protection nob setting xIN5 / 6 / 7 / 8 / 9 / 10
Equipment
-
Number of auxiliary contacts as normally closed contact0
-
Number of auxiliary contacts as normally open contact0
-
Number of auxiliary contacts as change-over contact0
-
Motor drive optionalYes
-
Can be accessorizedYes
Use cases
-
Category of useA
Standards
-
Standard textIEC 60947-2
Safety
-
REACH conformYes
-
RoHS conformYes
-
Halogen freeNo
Use conditions
-
Degree of pollution according to IEC 60664 / IEC 60947-23
-
Altitude2000 m
temperatur
-
Temperature of calibration50 °C
Downloads
-
Product image
-
Instruction manual
Instruction manuals for HHJ251DR
PDF10 MBInstruction manuals for HHJ251DR
PDF5 MB -
Declaration of conformity
EU Declaration of conformity for HHJ251DR
Declaration
PDF374 KBEU Declaration of conformity for HHJ251DR
Declaration
PDF355 KBEU Declaration of conformity for HHJ251DR
EU declaration of conformity
PDF569 KBEU Declaration of conformity for HHJ251DR
EU Declaration of Conformity
PDF588 KBEU Declaration of conformity for HHJ251DR
MCCB P630
PDF587 KBEU Declaration of conformity for HHJ251DR
Declaration
PDF332 KB -
PEP document
Product environmental profile for HHJ251DR
PDF464 KBProduct environmental profile for HHJ251DR
PDF432 KB -
RoHS report
Pollutant guidelines for HHJ251DR
RoHS declaration HHJ251DR (english)
PDF33 KBPollutant guidelines for HHJ251DR
REACH declaration HHJ251DR (english)
PDF32 KB
More documentation