Contactor 25A, 3NO, 230V~50/60Hz ESC325
EAN-Nr.
3250612400850
Packaging
1 piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical characteristics
Architecture
-
Type of orderNot applicable
-
Number of poles3 P
Configuration
-
Number of modules2
Main electrical features
-
Rated operational voltage Ue400 V
-
Frequency50 Hz
Voltage
-
Rated insulation voltage440 V
-
DC control voltage0 V
-
Command voltage AC230 V
-
Rated impulse withstand voltage4 kV
Electric current
-
Rated current25 A
-
Thermal rated current outside of housings25 A
-
Acceptable current load with AC7 category A25 A
-
Acceptable current load with AC7 category B8.5 A
Dimensions
-
Depth of installed product60 mm
-
Height of installed product83 mm
-
Width of installed product35.75 mm
Power
-
Inrush power absorbed9.2 W
-
Operating consumption1.85 W
-
Total power loss under IN5.5 W
-
Power loss per contact1.5 W
-
Power dissipation per coil1 W
-
Contact rating with 230 V in AC7 category A4.6 kW
-
Contact rating with 230 V in AC7 category B880 W
-
Contact rating with 400 V in AC7 category A13.8 kW
-
Contact rating with 400 V in AC7 category B2.6 kW
Tripping
-
Time of response when opening15 ms
-
Time of response when closing25 ms
Resistance
-
Winding resistance3150 Ω
Endurance
-
Electric endurance in number of cycles30000
-
Number of mechanical operations1000000
Fluorescent bulbs control
-
Max. power with fluorescent parallel lamps500 VA
-
Fluorescent lamps in duo circuit990 VA
-
Max. load fluorescent lamp490 VA
Incandescent bulbs control
-
Max. power with incandescent lamps1100 W
Installation, mounting
-
Tightening torque1,2Nm
Connection
-
Connection cross-sect. flexible conductor1 / 6mm²
-
Connection cross-sect. rigid cable1 / 10mm²
-
Number of contacts3
-
Type of contacts3NO
-
Type of connectionwith screw
-
Connection cross-section of the control cable solid1 / 10 mm²
Equipment
-
Can be accessorizedYes
Use
-
Local operation/hand operationNo
Standards
-
European directive WEEEnot concerned
Safety
-
Protection classisol.class II
Use conditions
-
Operating temperature-10…50 °C
-
Storage/transport temperature-40…80 °C
Downloads
-
Product image
-
Product data sheet
Product data sheets for ESC325
UK_MD_TDS_Contactors.pdf
PDF197 KB -
Declaration of conformity
EU Declaration of conformity for ESC325
Declaration
PDF385 KB -
PEP document
Product environmental profile for ESC325
PEP_Hager_ESC225_EN
PDF52 KB
More documentation