Output 6 -fold 16A C-Load adapted TXA206D
EAN
3250616049659
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Bus systemKNX
Functions
-
Multi-phase modesuitable to switch different external conductors
-
Switchingfor switching, e.g. of 6 independent loads
Configuration
-
Number of modules4
Controls and indicators
-
Indicator lampyes
-
Operationmanual operation can be activated via 2-level selection switch, thereby deactivation of the KNX function
-
Button / push-buttonwith illuminated programming button
Main electrical features
-
Rated operational voltage Ue230 V
-
Frequency50/60 Hz
Voltage
-
Max. switching capacity at230 V AC
-
Operating voltage over bus21…32 V DC
-
System supply voltage30V DC via bus
Electric current
-
Number of entry circuits0
-
Maximum through current16 A
-
Rated current16 A
-
Switching current at cos φ = 0.8max. 16 A
Dimensions
-
Width of rail mounted device (RMD)4 modules
-
Height90 mm
Power
-
Max. power with electronic transfo.1200 W
-
Total power loss under IN12 W
-
Output power2300 W
-
Max. switching power8625 W
-
Conventional transformers1600 VA
Lighting control
-
Fluorescent lamps with electronical ballast (EB)20 x 36 W
Fluorescent bulbs control
-
Energy-saving lamps18 x 23 W
-
Max. power fluo. duo lamp comp. series1500W - 200µF
LED control
-
LEDStatus LED integrated in manual operation button
Incandescent bulbs control
-
Max. power with incandescent lamps2300 W
Connection
-
Connection cross-sect. flexible conductor0,75 / 2,5mm²
-
Connection cross-sect. rigid cable0,75 / 2.5mm²
-
Conductor cross-section (flexible)0.75…2.5 mm²
-
Conductor cross-section (rigid)0.75…2.5 mm²
-
Type of contacts6NO
-
Bus coupling unitwith integral bus coupling unit
-
Type of connectionwith QuickConnect plug-in terminals
-
Bus connectionbus connection via connecting terminal
-
Type of connectionquick connect
Settings
-
Supported configuration modessystem
Scope of delivery
-
Bus connection includedYes
Equipment
-
Number of outputs6
-
Modular expandabilityNo
Use
-
Differentiation characteristic 3 - Saleswith plug-in terminals
Use conditions
-
Operating temperature0…45 °C
-
Storage/transport temperature-20…70 °C
Identification
-
Main design lineKNX
Downloads
-
Product image
-
ProductNotice
Instruction manuals for TXA206D
Module 6 sorties TXA206A, TXA206B, TXA206C, TXA206D
PDF1 MB -
ProductApplicationDescription
Application guides ETS / easy link for TXA206D
Description d'application TXA204_TXA206
PDF475 KBApplication guides ETS / easy link for TXA206D
Description d'application TXA206
PDF829 KB -
ProductTx100Description
Function descriptions TX100 for TXA206D
Description d'application TXA20Y
PDF728 KBFunction descriptions TX100 for TXA206D
Description d'application TXA204-206
PDF569 KB