Technical properties

Architecture
  • Type of order
    Toggle
  • Neutral position
    left
  • Number of protected poles
    4
  • Number of poles
    4 P
  • Type of pole
    4P4D N:0/50/100%
  • Type of case
    Fixed built-in
Functions
  • Complete device with protection unit
    Yes
  • Version as main switch
    Yes
  • Version as emergency stop installation
    No
  • Version as safety switch
    No
  • Version as maintenance-/service switch
    Yes
  • Trip Unit
    ENERGY
  • Integrated earth fault protection
    No
  • Concurrently switching N-neutral
    Yes
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 690 V
  • Type of supply voltage
    AC
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    800 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    400 A
  • Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
    12 kA
  • Rating current 10°C according to IEC 60947
    400 A
  • Rating current 15°C according to IEC 60947
    400 A
  • Rating current 20°C according to IEC 60947
    400 A
  • Rating current 25°C according to IEC 60947
    400 A
  • Rating current 30°C according to IEC 60947
    400 A
  • Rating current 35°C according to IEC 60947
    400 A
  • Rating current 40°C according to IEC 60947
    400 A
  • Rating current 45°C according to IEC 60947
    400 A
  • Rating current 50°C according to IEC 60947
    400 A
  • Rating current 55°C according to IEC 60947
    400 A
  • Rating current 60°C according to IEC 60947
    400 A
  • Rating current 65°C according to IEC 60947
    396 A
  • Rating current 70°C according to IEC 60947
    360 A
  • Rated service breaking capacity Ics under 660V AC according IEC 60947-2
    12 kA
  • Breaking capacity on 1 pole for IT 230V NF 60947-2
    10 kA
  • Breaking capacity on 1 pole for IT 400V NF 60947-2
    10 kA
  • Breaking capacity on 1 pole for IT 415V NF 60947-2
    10 kA
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2
    12 kA
Dimensions
  • Depth of installed product
    150 mm
  • Height of installed product
    260 mm
  • Width of installed product
    185 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Total power loss under IN
    90 W
  • Power loss per pole at In
    30 W
Tripping
  • Time of response when opening
    10 ms
Installation, mounting
  • Tightening torque
    18Nm
  • DIN rail mounting with optional adaptator
    No
  • Suitable for front mounting
    No
  • Suitable for ground mounting
    Yes
Connection
  • Connection
    Front connection
Cable
  • Cable Material
    Cu
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Motor drive optional
    Yes
  • Can be accessorized
    Yes
Use cases
  • Category of use
    B
Standards
  • Standard text
    IEC 60947-2
  • European directive WEEE
    concerned
Safety
  • REACH conform
    No
  • RoHS conform
    Yes
  • Halogen free
    No
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m