The Hager h3+ P160 TM adjustable 4P4D 25A MCCB protects three-phase + neutral circuits in distribution boards. With Icu 25 kA at 400 V (35 kA at 230/240 V) and Ue up to 690 V, it ensures dependable short-circuit and overload protection. Adjustable thermal 0.63-1 x In and magnetic 6-12 x In enable precise coordination. Fixed, toggle-operated, IP4X, interlockable. Suits 6-95 mm² Cu/Al, 50-60 Hz. High endurance: 10k/40k cycles.
EAN
3250613187279
Packaging
1 Piece
Moulded Case Circuit Breaker 4P 630A 25kA LSNI fixed toggle IP4X HHS026DR
Complete your system
Optional accessories
-
Under voltage coil 8 products available -
Connection Functions 6 products available -
Handle with interlock for power breaker 1 products available -
Shunt release 5 products available -
Auxiliaries cable adaptor 2 products available -
Auxiliaries contact block 5 products available
Complete your system
Technical properties
Electric current
-
Rated current IN25 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-225 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-235 kA
-
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-235 kA
-
Rated service breaking capacity Ics under 400 V AC according to IEC 60947-225 kA
-
Rated ultimate short-circuit breaking capacity Icu under 660 V AC IEC 60947-26 kA
-
Rated ultimate short-circuit breaking capacity Icu under 690 V AC IEC 60947-26 kA
-
Rated current 10°C according to IEC 6094730.10 A
-
Rated current 15°C according to IEC 6094729.60 A
-
Rated current 20°C according to IEC 6094728.90 A
-
Rated current 25°C according to IEC 6094728.30 A
-
Rated current 30°C according to IEC 6094727.70 A
-
Rated current at 35°C according to IEC 6094727 A
-
Rated current at 40°C according to IEC 6094726.40 A
-
Rated current 45°C according to IEC 6094725.70 A
-
Rated current 50°C according to IEC 6094725 A
-
Rated current 55°C according to IEC 6094724.30 A
-
Rated current at 60°C according to IEC 6094723.50 A
-
Rated current 65°C according to IEC 6094722.80 A
-
Rated current 70°C according to IEC 6094722 A
Architecture
-
Number of poles4
-
Control/operation elementToggle
-
Device construction typeFixed built-in
-
Neutral positionLeft
Frequency
-
Frequency50 - 60 Hz
Voltage
-
Rated impulse withstand voltage Uimp8000 V
-
Rated insulation voltage Ui800 V
-
Rated operational voltage Ue220 - 690 V
Functions
-
Trip unitTM A/A
Power
-
Power dissipation at IN19.50 W
Endurance
-
Electric endurance in number of cycles10000
-
Number of mechanical operations40000
Safety
-
Ingress Protection (IP) classIP4X
Connection
-
Cross-section flexible conductor6 - 70 mm²
-
Cross-section rigid conductor6 - 95 mm²
Cover, door
-
InterlockableYes
Settings
-
Thermal protection knob setting xIN0.63, 0.8, 1
Cable
-
Cable materialCopper, Aluminium
Compatibility
-
Compatible with RDC AOBNo
-
Suitable for DIN RailNo
-
Suitable for distribution boardYes
Dimensions
-
Height130 mm
-
Width120 mm
-
Depth97 mm
Electrical protection
-
Instantaneous protection (li): dial setting coefficient6, 8, 10, 12
Installation, mounting
-
Mounting-/Connection PositionFront
-
Nominal tightening torque6 - 6 Nm
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More
Certifications and documents
Downloads
More documentation