The Hager h3+ P250 TM ADJ 4P4D MCCB delivers reliable main or feeder protection for commercial/industrial boards. Rated 250A (50°C), 4-pole with left neutral, 220-690V, 50/60Hz. High breaking capacity: Icu 70kA at 400V (85kA at 230/240V), Ics 50kA at 400V. Adjustable thermal 0.63-1×In and instantaneous 6-10×In. Fixed front-mount, IP4X, Cu/Al 35-185 mm². 40k mechanical/10k electrical operations.
EAN
3250613170790
Packaging
1 Piece
Complete your system
Optional accessories
-
Chassis power breaker 4 products available -
Auxiliaries contact block 5 products available -
Auxiliaries cable adaptor 2 products available -
Connection Functions 8 products available -
Under voltage coil 8 products available -
Shunt release 5 products available
Complete your system
Technical properties
Electric current
-
Rated current250 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-270 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-285 kA
-
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-285 kA
-
Rated service breaking capacity Ics under 400 V AC according to IEC 60947-250 kA
-
Rated ultimate short-circuit breaking capacity Icu under 660 V AC IEC 60947-26 kA
-
Rated ultimate short-circuit breaking capacity Icu under 690 V AC IEC 60947-26 kA
-
Rated current 10°C according to IEC 60947310.20 A
-
Rated current 15°C according to IEC 60947303.30 A
-
Rated current 20°C according to IEC 60947296.30 A
-
Rated current 25°C according to IEC 60947289.10 A
-
Rated current 30°C according to IEC 60947281.70 A
-
Rated current at 35°C according to IEC 60947274.10 A
-
Rated current at 40°C according to IEC 60947266.30 A
-
Rated current 45°C according to IEC 60947258.30 A
-
Rated current 50°C according to IEC 60947250 A
-
Rated current 55°C according to IEC 60947241.40 A
-
Rated current at 60°C according to IEC 60947232.50 A
-
Rated current 65°C according to IEC 60947223.30 A
-
Rated current 70°C according to IEC 60947213.70 A
Architecture
-
Number of poles4
-
Control/operation elementToggle
-
Device construction typeFixed built-in
-
Neutral positionLeft
Frequency
-
Frequency50 - 60 Hz
Voltage
-
Rated impulse withstand voltage Uimp8000 V
-
Rated insulation voltage Ui800 V
-
Rated operational voltage Ue220 - 690 V
Functions
-
Trip unitTM A/A
Power
-
Total power loss under IN50.70 W
Endurance
-
Electric endurance in number of cycles10000
-
Number of mechanical operations40000
Safety
-
Ingress Protection (IP) classIP4X
Connection
-
Cross-section flexible conductor35 - 150 mm²
-
Cross-section rigid conductor35 - 185 mm²
Cover, door
-
InterlockableYes
Settings
-
Thermal protection knob setting xIN0.63, 0.8, 1
Cable
-
Cable materialCopper, Aluminium
Compatibility
-
Compatible with RDC AOBYes
-
Suitable for DIN RailNo
-
Suitable for distribution boardYes
Dimensions
-
Height165 mm
-
Width140 mm
-
Depth97 mm
Electrical protection
-
Instantaneous protection (li): dial setting coefficient6, 7, 8, 9, 10
Installation, mounting
-
Mounting-/Connection PositionFront
-
Nominal tightening torque12 - 12 Nm
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More
Certifications and documents
Downloads
-
Product datasheet
Hager Product data sheet HET251DR
Moulded Case Circuit Breaker h3+ P250 TM ADJ 4P4D N0-100% 250A 70kA FTC
PDF -
STEP files
CAD file for MCCB 250A 4P
STEP files International 2026-04-15
STP805,89 kB -
Declaration of conformity
Declaration
Declaration of conformity International 2022-04-25
PDF461,97 kBDeclaration of conformity en-US 2026-07-14
PDF346,64 kB
More documentation