The Hager h3 x160 TM FIX 3P3D 40A MCCB protects three-phase circuits in commercial and industrial panels. Icu 18kA at 400V (25kA at 240V) and Ics up to 25kA ensure safe fault interruption. TM trip unit with 10 ms opening. Ue 220-415V, Ui 690V, Uimp 8kV. IP4X, 50/60Hz. Fixed 3-pole toggle, screw terminals (4-95 mm²). DIN-rail compatible. Electrical endurance 10,000 operations.
EAN
3250613136086
Packaging
1 Piece
Complete your system
Optional accessories
-
Auxiliaries contact block 4 products available -
Shunt release 5 products available -
Under voltage coil 8 products available -
Connection Functions 4 products available -
AOB MCCB type A-HI 2 products available -
Terminal cover 4 products available
Complete your system
Technical properties
Electric current
-
Rated current IN40 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-218 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-225 kA
-
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-225 kA
-
Rated service breaking capacity Ics under 400 V AC according to IEC 60947-218 kA
-
Rated current 10°C according to IEC 6094749.50 A
-
Rated current 15°C according to IEC 6094748.40 A
-
Rated current 20°C according to IEC 6094747.30 A
-
Rated current 25°C according to IEC 6094746.10 A
-
Rated current 30°C according to IEC 6094745 A
-
Rated current at 35°C according to IEC 6094743.80 A
-
Rated current at 40°C according to IEC 6094742.50 A
-
Rated current 45°C according to IEC 6094741.30 A
-
Rated current 50°C according to IEC 6094740 A
-
Rated current 55°C according to IEC 6094738.60 A
-
Rated current at 60°C according to IEC 6094737.20 A
-
Rated current 65°C according to IEC 6094735.70 A
-
Rated current 70°C according to IEC 6094734.20 A
Architecture
-
Number of poles3
-
Control/operation elementToggle
-
Device construction typeFixed built-in
-
Neutral positionWithout neutral
Tripping
-
Response time when opening10 ms
Frequency
-
Frequency50 - 60 Hz
Voltage
-
Rated impulse withstand voltage Uimp8000 V
-
Rated insulation voltage Ui690 V
-
Rated operational voltage Ue220 - 415 V
Functions
-
Trip unitTM F/F
Power
-
Power dissipation at IN11 W
Endurance
-
Electric endurance in number of cycles10000
-
Number of mechanical operations20000
Safety
-
Ingress Protection (IP) classIP4X
Connection
-
Cross-section flexible conductor4 - 70 mm²
-
Cross-section rigid conductor4 - 95 mm²
Installation, mounting
-
Mounting-/Connection PositionFront
-
Nominal tightening torque down terminal5 - 5 Nm
-
Nominal tightening torque top terminal5 - 5 Nm
Connectivity
-
Type of connectionScrew terminal
Settings
-
Thermal protection knob setting xIN1, 1
Cable
-
Cable materialCopper
Dimensions
-
Height130 mm
-
Width75 mm
-
Depth68 mm
-
Downstream busbar: width, height, diameter screw (max.)130 mm, 75 mm
Compatibility
-
Compatible with RDC AOBYes
-
Suitable for DIN RailYes
Main electrical attributes
-
Magnetic protection trip time0 - 0 ms
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More
Certifications and documents
Downloads
-
Product datasheet
Hager Product data sheet HDA040Z
Moulded Case Circuit Breaker h3 x160 TM FIX 3P3D 40A 18kA CTC
PDF -
Installation manual
Installation manual International 2021-06-07
PDF8,51 MB -
Declaration of conformity
Declaration of conformity en-US 2026-07-14
PDF346,59 kB
UKCA Declaration of Conformity
Declaration of conformity en-GB 2025-03-20
PDF435,49 kB
More documentation