SPD T2 2P pluggable 40kA photovoltaic SPV340
EAN
3250615514967
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Complete your system
Optional accessories
-
Surge protection device for power supply systems 1 products available
Complete your system
Technical properties
Capacity
-
Number of modules3
Voltage
-
Rated operational voltage Ue1,000 - 1,000 V
-
Continuous operating voltage Uc according to IEC 61643-11,170 V
-
Voltage protection level Up according to IEC 61643-13.70 kV
-
Voltage protection level Up L-PE/N-PE according to IEC 61643-113.70 kV
-
Voltage level Up L-N/PEN IEC 61643-113,700 V
Electric current
-
Nominal discharge current In 8 - 20 µs L-N(PEN)/N-PE IEC 6164315 kA
-
Max. discharge (Imax) L-N(PEN)/ N-PE40 kA
Dimensions
-
Height89.80 mm
-
Width53.40 mm
-
Depth56.1 mm
Use conditions
-
Operating temperature-40 - 80 °C
Network configuration
-
Network typeDC
Equipment
-
With remote signalling contactNo
Connection
-
Cross-section of input and output with screws, for flexible conductors1.5 - 25 mm²
-
Cross-section of input and output with screws, for massive conductors1.5 - 35 mm²
-
Cross-section signal contact0.14 - 1.5 mm²
Standards
-
Requirement class IEC 61643T2
Frequency
-
Frequency50 - 60 Hz
Installation, mounting
-
Nominal tightening torque3 - 4.5 Nm
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers Learn More
Certifications and documents
Downloads
-
Product image
-
Declaration of conformity
Declaration of conformity for Lightning rod T2 photovoltaic
Declaration of conformity International 2020-11-27
PDF250,50 kB
More documentation