MCB 3P 10kA/15kA D-1A 3M NDN301A
EAN
3250614619175
Packaging
4 Pieces
Login to create a product list
You need to be logged into your myHager account to create product lists
Complete your system
Optional accessories
-
Auxiliaries contact block 2 products available
-
Shunt release 1 products available
-
Under voltage coil 1 products available
-
Phase separation functions 1 products available
-
Locking interlocking functions 1 products available
-
See more 5 other products available
Complete your system
Technical properties
Electric current
-
Rated current1 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-215 kA
-
Rated current -25°C1.41 A
-
Rated current at -20°C1.37 A
-
Rated current -15°C1.34 A
-
Rated current -10°C1.31 A
-
Rated current -5°C1.27 A
-
Rated current at 0°C1.24 A
-
Rated current 5°C1.20 A
-
Rated current 10°C1.16 A
-
Rated current 15°C1.13 A
-
Rated current at 20°C1.09 A
-
Rated current 25°C1.04 A
-
Rated current 30°C1 A
-
Rated current 35°C0.95 A
-
Rated current at 40°C0.90 A
-
Rated current at 45°C0.84 A
-
Rated current at 50°C0.78 A
-
Rated current 55°C0.72 A
-
Rated current 60°C0.65 A
-
Rated current 65°C0.57 A
-
Rated current 70°C0.48 A
Architecture
-
Type of pole3P
-
CurveD
Capacity
-
Number of modules3
Main electrical attributes
-
Rated short-circuit breaking capacity Icn AC according to IEC 60898-110 kA
-
Nominal tightening torque top terminal2.80 - 2.80 Nm
-
Nominal tightening torque down terminal2.80 - 2.80 Nm
Voltage
-
Rated operational voltage Ue400 - 400 V
-
Type voltage supplyAC
-
Rated insulation voltage Ui500 V
-
Rated impulse withstand voltage Uimp6,000 V
Frequency
-
Frequency50 - 60 Hz
Connection
-
Cross-section of input and output with screws, for massive conductors1 - 35 mm²
-
Cross-section of input and output with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for massive conductors1 - 35 mm²
Installation, mounting
-
Nominal tightening torque2.80 - 2.80 Nm
-
Type of bottom connection for modular devicesbiconnect
-
Type of top connection for modular devicesScrew terminal
-
360° mounting position possibleYes
Safety
-
Ingress Protection (IP) classIP20
Use conditions
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Operating temperature-25 - 70 °C
Power
-
Total power loss under IN3.24 W
Endurance
-
Electric endurance in number of cycles4,000
-
Number of mechanical operations20,000
Connectivity
-
Type of connectionScrew terminal
-
Top connection alignment for modular devicesAligned terminal
-
Down connection alignment for modular devicesAligned terminal
Dimensions
-
Height83 mm
-
Width52.50 mm
-
Depth70 mm
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers Learn More
Certifications and documents
Downloads
More documentation