Magnetic MCB 3P 25kA 4A 400V Zubehörmöglich. Anzeige IEC 947-2 MMN304

EAN
3250614440151
Packaging
1 Piece

Technical properties

Architecture
  • Neutral position
    not applicable
  • Number of protected poles
    3
  • Number of poles
    3 P
  • Type of pole
    3 P
  • Fixing mode
    DIN rail type O (symmetrical)
Functions
  • Concurrently switching N-neutral
    No
Configuration
  • Number of modules
    3
Connectivity
  • Top connection alignement for modular devices
    Aligned terminal
  • Bottom connection alignement for modular devices
    Aligned terminal
Main electrical features
  • Rated operational voltage Ue
    415 V
  • Type of supply voltage
    AC
Voltage
  • Rated insulation voltage
    500 V
  • Rated impulse withstand voltage
    6000 V
Electric current
  • Rated current
    4 A
  • Magnetic regulating currrent
    12 In
  • Rating current -10°C according to IEC 60947
    4 A
  • Rating current -15°C according to IEC 60947
    4 A
  • Rating current -20°C according to IEC 60947
    4 A
  • Rating current -25°C according to IEC 60947
    4 A
  • Rating current -5°C according to IEC 60947
    4 A
  • Rating current 0°C according to IEC 60947
    4 A
  • Rating current 10°C according to IEC 60947
    4 A
  • Rating current 15°C according to IEC 60947
    4 A
  • Rating current 20°C according to IEC 60947
    4 A
  • Rating current 25°C according to IEC 60947
    4 A
  • Rating current 30°C according to IEC 60947
    4 A
  • Rating current 35°C according to IEC 60947
    4 A
  • Rating current 40°C according to IEC 60947
    4 A
  • Rating current 45°C according to IEC 60947
    4 A
  • Rating current 5°C according to IEC 60947
    4 A
  • Rating current 50°C according to IEC 60947
    4 A
  • Rating current 55°C according to IEC 60947
    4 A
  • Rating current 60°C according to IEC 60947
    4 A
  • Rating current 65°C according to IEC 60947
    4 A
  • Rating current 70°C according to IEC 60947
    4 A
  • Breaking capacity on 1 pole for IT 400V NF 60947-2
    3 kA
  • Breaking capacity on 1 pole for IT 415V NF 60947-2
    3 kA
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    25 kA
Current correction factors
  • Correction factor of rating current for 2 devices placed side-by-side
    1
  • Correction factor of rating current for 3 devices placed side-by-side
    0.95
  • Correction factor of rating current for 4 and 5 devices placed side-by-side
    0.9
  • Correction factor of rating current for 6 devices placed side-by-side
    0.85
  • Correction factor of magnetic tripping with 100 Hz
    1.1
  • Correction factor of magnetic tripping with 200 Hz
    1.2
  • Correction factor of magnetic tripping with 400 Hz
    1.5
  • Correction factor of magnetic tripping with 60 Hz
    1
Dimensions
  • Depth of installed product
    70 mm
  • Height of installed product
    83 mm
  • Width of installed product
    52.5 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Maximum power loss per pole according to the product standard
    3 W
  • Total power loss under IN
    0.4 W
  • Power loss per pole at In
    0.1 W
Tripping
  • Time of response when opening
    7 ms
Installation, mounting
  • Type of top connection for modular devices
    with screw
  • Tightening torque
    2,8Nm
  • Type of top rail clip for modular devices
    Plastic
  • Type of bottom rail clip for modular devices
    plastic
  • Type of Bottom Connection for modular devices
    BIconnect
  • Top removability for modular devices
    Yes
  • Bottom removability for modular devices
    Yes
  • Suitable for flush-mounting
    Yes
Connection
  • Connection cross-section at output with screw, for flexible conductor
    1 / 25 mm²
  • Connection cross-section at output with screw, for massive conductor
    1 / 35 mm²
  • Connection cross-section for rigid conductor, upstream terminals with screws
    1 / 35 mm²
  • Connection cross-section of the access with screws, with flexible conductor
    1 / 25 mm²
  • Downstream cage clamp delivery status
    opened
  • Upstream cage clamp delivery status
    opened
Equipment
  • Can be accessorized
    Yes
  • With transparent product label holder
    Yes
Standards
  • Standard text
    IEC 60947-2
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP20
  • REACH conform
    No
  • RoHS conform
    Yes
  • Halogen free
    No
Use conditions
  • Operating temperature
    -25…70 °C
  • Altitude
    2000 m
  • Storage/transport temperature
    -25…80 °C