The Hager h3 x160 TM FIX 3P3D 80A 18kA moulded case circuit breaker safeguards three-phase circuits against overloads and short circuits. Icu: 18 kA at 400 V (25 kA at 240 V). Ui 690 V, Uimp 8 kV. Fixed thermal‑magnetic trip for fast opening (~10 ms). 3-pole, IP4X, 50-60 Hz, screw terminals, DIN-rail suitable. Robust and compact for industrial and commercial distribution boards.
EAN
3250613136116
Packaging
1 Piece
Complete your system
Optional accessories
-
Auxiliaries contact block 4 products available -
Shunt release 5 products available -
Under voltage coil 8 products available -
Connection Functions 4 products available -
AOB MCCB type A-HI 2 products available -
Terminal cover 4 products available
Complete your system
Technical properties
Electric current
-
Rated current IN80 A
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-218 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-225 kA
-
Rated service breaking capacity Ics under 230 V AC according to IEC 60947-225 kA
-
Rated ultimate short-circuit breaking capacity Icu under 690 V AC IEC 60947-24 kA
-
Rated service breaking capacity Ics under 400 V AC according to IEC 60947-218 kA
-
Rated current 10°C according to IEC 60947101.90 A
-
Rated current 15°C according to IEC 6094799.40 A
-
Rated current 20°C according to IEC 6094796.90 A
-
Rated current 25°C according to IEC 6094794.30 A
-
Rated current 30°C according to IEC 6094791.60 A
-
Rated current at 35°C according to IEC 6094788.80 A
-
Rated current at 40°C according to IEC 6094786 A
-
Rated current 45°C according to IEC 6094783 A
-
Rated current 50°C according to IEC 6094780 A
-
Rated current 55°C according to IEC 6094776.80 A
-
Rated current at 60°C according to IEC 6094773.40 A
-
Rated current 65°C according to IEC 6094770 A
-
Rated current 70°C according to IEC 6094766.30 A
Architecture
-
Number of poles3
-
Control/operation elementToggle
-
Device construction typeFixed built-in
-
Neutral positionWithout neutral
Tripping
-
Response time when opening10 ms
Frequency
-
Frequency50 - 60 Hz
Voltage
-
Rated impulse withstand voltage Uimp8000 V
-
Rated insulation voltage Ui690 V
-
Rated operational voltage Ue220 - 415 V
Functions
-
Trip unitTM F/F
Power
-
Power dissipation at IN18.90 W
Endurance
-
Electric endurance in number of cycles10000
-
Number of mechanical operations20000
Safety
-
Ingress Protection (IP) classIP4X
Connection
-
Cross-section flexible conductor4 - 70 mm²
-
Cross-section rigid conductor4 - 95 mm²
Installation, mounting
-
Nominal tightening torque6 - 6 Nm
-
Mounting-/Connection PositionFront
-
Nominal tightening torque down terminal5 - 5 Nm
-
Nominal tightening torque top terminal5 - 5 Nm
Connectivity
-
Type of connectionScrew terminal
Settings
-
Thermal protection knob setting xIN1, 1
-
Adjustment range short-term delayed short-circuit release0 - 0 A
Cable
-
Cable materialCopper
Dimensions
-
Height130 mm
-
Width75 mm
-
Depth68 mm
-
Downstream busbar: width, height, diameter screw (max.)130 mm, 75 mm
Compatibility
-
Compatible with RDC AOBYes
-
Suitable for DIN RailYes
Main electrical attributes
-
Magnetic protection trip time0 - 0 ms
Downloads
-
Product datasheet
Hager Product data sheet HDA080Z
Moulded Case Circuit Breaker X160 3P 18kA 80A
PDF -
Installation manual
Installation manual International 2021-06-07
PDF8,51 MB -
Declaration of conformity
Declaration of conformity en-US 2026-07-14
PDF346,59 kB
UKCA Declaration of Conformity
Declaration of conformity en-GB 2025-03-20
PDF435,49 kB
More documentation