RCCB 2M 1P+N 40A 30mA AC CD640B
EAN-Nr.
3250611640028
Packaging
1 piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical characteristics
Electric current
-
Rated current40 A
-
Rated residual operating current Idn30 mA
-
Breaking and opening capacity Idm0,50 kA
-
Rated conditional short-circuit current Inc according to EN61008-16 kA
Installation, mounting
-
Nominal tightening torque1,90 - 1,90 Nm
Voltage
-
Rated operational voltage Ue230 - 230 V
-
Rated insulation voltage Ui500 V
-
Rated impulse withstand voltage Uimp4000 V
-
Max. operating voltage253 V
Frequency
-
Frequency50 - 50 Hz
Capacity
-
Number of modules2
Safety
-
Residual current typeAC
-
Ingress Protection (IP) classIP20
Use conditions
-
Air humidity protectionFor all climates
-
Max. Altitude2000 m
Endurance
-
Electric endurance in number of cycles2000
-
Number of mechanical operations4000
Connectivity
-
Type of connectionScrew terminal
-
Top connection alignment for modular devicesShifted terminal
Dimensions
-
Height84 mm
-
Width35 mm
-
Depth68 mm