The Hager MCB 1P 10kA/15kA C-10A 1M miniature circuit breaker protects circuits from overloads and short circuits. With C-curve 10A, 10kA Icn (IEC 60898-1) and 15kA Icu (IEC 60947-2), it suits residential and light commercial boards. 1-module, 230-400 V AC, 50-60 Hz. Screw top and biconnect bottom for fast wiring, IP20, 6 kV impulse, -25…70 °C, 20,000 mech ops. 360° mounting saves panel space.
EAN
3250614615504
Packaging
12
MCB 1P 16A Curve B 10kA Icn / 15kA Icu 1 Module NCN110A
Complete your system
Optional accessories
-
Terminal cover 1 products available -
Modular phase busbar 2 products available
Complete your system
Technical properties
Electric current
-
Rated current10 A
-
Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 60898-110 kA
-
Rated ultimate short-circuit breaking capacity Icu AC IEC 60947-215 kA
-
Rated current -15°C12.39 A
-
Rated current -10°C12.15 A
-
Rated current -5°C11.90 A
-
Rated current at 0°C11.65 A
-
Rated current 5°C11.39 A
-
Rated current 10°C11.13 A
-
Rated current 15°C10.86 A
-
Rated current at 20°C10.58 A
-
Rated current 25°C10.29 A
-
Rated current 30°C10 A
-
Rated current 35°C9.70 A
-
Rated current at 40°C9.39 A
-
Rated current at 45°C9.06 A
-
Rated current at 50°C8.73 A
-
Rated current 55°C8.38 A
-
Rated current 60°C8.02 A
-
Rated current 65°C7.64 A
-
Rated current 70°C7.24 A
-
Rated service breaking capacity Ics AC according to IEC 60898-17.50 kA
Architecture
-
Type of pole1P
-
CurveC
Capacity
-
Number of modules1
Main electrical attributes
-
Rated short-circuit breaking capacity Icn AC according to IEC 60898-110 kA
Installation, mounting
-
Nominal tightening torque top terminal2.80 - 2.80 Nm
-
Nominal tightening torque down terminal2.80 - 2.80 Nm
-
Nominal tightening torque2.80 - 2.80 Nm
-
Type of bottom connection for modular devicesbiconnect
-
Type of top connection for modular devicesScrew terminal
-
360° mounting position possibleYes
Voltage
-
Rated operational voltage Ue230 - 400 V
-
Type voltage supplyAC
-
Rated insulation voltage Ui500 V
-
Rated impulse withstand voltage Uimp6000 V
Frequency
-
Frequency50 - 60 Hz
Connection
-
Cross-section of input and output with screws, for massive conductors1 - 35 mm²
-
Cross-section of input and output with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for flexible conductors1 - 25 mm²
-
Cross-section of input with screws, for massive conductors1 - 35 mm²
Safety
-
Ingress Protection (IP) classIP20
-
Grid distance60 mm
Use conditions
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Class of energy limitation I²t3
-
Operating temperature-25 - 70 °C
Power
-
Total power loss under IN1.87 W
Connectivity
-
Type of connectionScrew terminal
-
Top connection alignment for modular devicesAligned terminal
-
Down connection alignment for modular devicesAligned terminal
Dimensions
-
Height83 mm
-
Width17.50 mm
-
Depth70 mm
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More
Certifications and documents
Downloads
-
Product datasheet
Hager Product data sheet NCN110A
MCB 1P 10kA/15kA C-10A 1M
PDF -
Declaration of conformity
UKCA Declaration of Conformity
Declaration of conformity en-GB 2024-10-02
PDF653,93 kB
More documentation