Service Temporarily Unavailable

The server is temporarily unable to service your request due to maintenance downtime or capacity problems. Please try again later.

MCCB h3+ P250 TM 3x63A 40kA • HNT063DR | Hager

Moulded Case Circuit Breaker h3+ P250 TM ADJ 3P3D 63A 40kA FTC HNT063DR

EAN
3250613154813
Packaging
1 Piece

Complete your system

Optional accessories

  • See more (30)
    • Terminal cover 4 products available
    • Shunt release 4 products available
    • Auxil­i­aries contact block 6 products available
    • Connec­tion Func­tions 3 products available
    • Handle with inter­lock for power breaker 1 products available
    • Handle for power circuit breaker 1 products available

    Technical properties

    Elec­tric current
    • Rated current
      63 A
    • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 400 V AC IEC 60947-2
      40 kA
    • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 240 V AC IEC 60947-2
      50 kA
    • Rated service breaking capa­city Ics under 230 V AC according to IEC 60947-2
      50 kA
    • Rated service breaking capa­city Ics under 400 V AC according to IEC 60947-2
      40 kA
    • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 660 V AC IEC 60947-2
      6 kA
    • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 690 V AC IEC 60947-2
      6 kA
    • Rated current 10°C according to IEC 60947
      83,10 A
    • Rated current 15°C according to IEC 60947
      80,90 A
    • Rated current 20°C according to IEC 60947
      78,60 A
    • Rated current 25°C according to IEC 60947
      76,20 A
    • Rated current 30°C according to IEC 60947
      73,70 A
    • Rated current at 35°C according to IEC 60947
      71,20 A
    • Rated current at 40°C according to IEC 60947
      68,60 A
    • Rated current 45°C according to IEC 60947
      65,90 A
    • Rated current 50°C according to IEC 60947
      63 A
    • Rated current 55°C according to IEC 60947
      60 A
    • Rated current at 60°C according to IEC 60947
      56,90 A
    • Rated current 65°C according to IEC 60947
      53,50 A
    • Rated current 70°C according to IEC 60947
      50 A
    Archi­tec­ture
    • Number of poles
      3
    • Control/­op­er­a­tion element
      Toggle
    • Device construc­tion type
      Fixed built-in
    • Neutral posi­tion
      Without neutral
    Frequency
    • Frequency
      50 - 60 Hz
    Voltage
    • Rated impulse with­stand voltage Uimp
      8000 V
    • Rated insu­la­tion voltage Ui
      800 V
    • Rated oper­a­tional voltage Ue
      220 - 690 V
    Func­tions
    • Trip unit
      TM A/A
    Power
    • Total power loss under IN
      13,95 W
    Endur­ance
    • Elec­tric endur­ance in number of cycles
      10000
    • Number of mech­an­ical oper­a­tions
      40000
    Safety
    • Ingress Protec­tion (IP) class
      IP4X
    Connec­tion
    • Cross-sec­tion flex­ible conductor
      35 - 150 mm²
    • Cross-sec­tion rigid conductor
      35 - 185 mm²
    Cover, door
    • Inter­lock­able
      Yes
    Settings
    • Thermal protec­tion knob setting xIN
      0.63, 0.8, 1
    Cable
    • Cable material
      Copper, Aluminium
    Compat­ib­ility
    • Compat­ible with RDC AOB
      No
    • Suit­able for DIN Rail
      No
    • Suit­able for distri­bu­tion board
      Yes
    Dimen­sions
    • Height
      165 mm
    • Width
      105 mm
    • Depth
      97 mm
    Elec­trical protec­tion
    • Instant­an­eous protec­tion (li): dial setting coef­fi­cient
      6, 8, 10, 13
    Install­a­tion, mounting
    • Mount­ing-/­Con­nec­tion Posi­tion
      Front
    • Nominal tight­ening torque
      12 - 12 Nm

    Environmental value

    We are committed to improve our environmental performance by reducing our carbon footprint. Learn More

    RoHS conform Yes
    REACh-SVHC free Yes