Binary input 4 fold, flush mounted, KNX TXB304

EAN
3250616049413
Packaging
1 Piece

This product is now obsolete. However, this page remains available for information purposes. If you require any further information for an alternative solution please contact your closest Hager official distributor. Closest wholesaler


Technical properties

Architecture
  • Bus system
    EIB
  • Fixing mode
    flush-mounting
Functions
  • Bus module detachable
    No
  • Easy link functions
    Switching functions, dimming functions, blind control functions functions, priority functions, scene functions, heating functions and timer functions
  • ETS additional functions
    ETS additional functions: value transmitter 1 and 2 bytes, 2-channel mode, level switch function
Configuration
  • Number of modules
    0
Compatibility
  • Extension unit
    extension unit for light scene push-button
Controls and indicators
  • Button / push-button
    with programming button and red programming LED
Connectivity
  • Binary inputs
    with 2 independent binary inputs for potential-free contacts ; with 2 freely parameterisable outputs for LED activation
Voltage
  • Input voltage
    5 V
  • Operating voltage over bus
    21…32 V DC
  • System supply voltage
    30V DC via bus
Electric current
  • Number of entry circuits
    4
  • Intensity by input
    0.5 mA
Dimensions
  • Dimensions (LLxwwxhh)
    38 x 35 x 12 mm
  • Width of rail mounted device (RMD)
    0 modules
Length
  • Max distance to switches
    5 mm
Measurement
  • Input scanning voltage
    per channel 5 V
Materials
  • Colour
    stone grey
Installation, mounting
  • Installation mode
    for flush-mounted and hollow-wall mounting
Connection
  • Conductor cross-section (flexible)
    0.75…2.5 mm²
  • Conductor cross-section (rigid)
    0.75…2.5 mm²
  • Connection to
    Potential free, switch, push button, automation system
  • Bus coupling unit
    with integral bus coupling unit
  • Bus connection
    bus connection via connecting terminal
Cable
  • Cable length extendable to
    max. 5 m
Settings
  • Supported configuration modes
    system, easy
Scope of delivery
  • Bus connection included
    Yes
Equipment
  • Number of outputs
    0
Use
  • Differentiation characteristic 3 - Sales
    with integral bus coupling unit
Safety
  • REACH conform
    No
  • RoHS conform
    Yes
  • Halogen free
    No
Use conditions
  • Operating temperature
    0…45 °C
  • Storage/transport temperature
    -20…70 °C
Identification
  • Main design line
    KNX