Output 10 -fold 16A TXA207C
EAN
3250616049772
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Bus systemEIB
Functions
-
Multi-phase modesuitable to switch different external conductors
Configuration
-
Number of modules6
Controls and indicators
-
Indicator lampyes
Main electrical features
-
Rated operational voltage Ue230 V
Voltage
-
Operating voltage over bus21…32 V DC
-
System supply voltage30V DC via bus
Electric current
-
Number of entry circuits0
-
Maximum through current16 A
-
Rated current16 A
Power
-
Max. power with electronic transfo.1200 W
-
Total power loss under IN15 W
-
Output power1200 W
-
Max. switching power7500 W
Fluorescent bulbs control
-
Max. power fluo. duo lamp comp. series20 x 36 W
Incandescent bulbs control
-
Max. power with incandescent lamps2300 W
Connection
-
Connection cross-sect. flexible conductor0,75 / 2,5mm²
-
Connection cross-sect. rigid cable0,75 / 2.5mm²
-
Type of contacts10NO
-
Bus coupling unitwith integral bus coupling unit
-
Bus connectionbus connection via connecting terminal
-
Type of connectionquick connect
Scope of delivery
-
Bus connection includedYes
Equipment
-
Number of outputs10
-
Bidirectional radio frequencyNo
-
Modular expandabilityNo
Use conditions
-
Operating temperature0…45 °C
-
Storage/transport temperature-20…70 °C
Identification
-
Main design lineKNX
Downloads
-
Product image
-
ProductNotice
Instruction manuals for TXA207C
Module 10 sorties 230V TXA207A, TXA207B, TXA207C, TXA207D
PDF1 MB -
ProductETSBase
Product-Database ETS for TXA207C
Logiciel d'application ETS du TXA207Y
VD2672 KB -
ProductTx100Description
Function descriptions TX100 for TXA207C
Description d'application TXA20Y
PDF728 KB