MCB 3P 10kA/15kA D-63A 3M NDN363A
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
-
Neutral positionwithout neutral
-
Number of protected poles3
-
Number of poles3 P
-
Type of pole3 P
-
CurveD
-
Concurrently switching N-neutralNo
-
Number of modules3
-
Top connection alignement for modular devicesAligned terminal
-
Bottom connection alignement for modular devicesAligned terminal
-
Rated short circuit breaking capacity Icn AC according IEC60898-110 kA
-
Rated operational voltage Ue400 V
-
Type of supply voltageAC
-
Rated insulation voltage500 V
-
Rated impulse withstand voltage6000 V
-
Minimum threshold voltage (Ue min)12 V
-
Rated current63 A
-
Rated service breaking capacity Ics AC according IEC 60898-17.5 kA
-
min/maxi threshold value of the AC thermal operation1.13 / 1.45 In
-
Magnetic regulating currrent10 / 14.4 In
-
min/maxi threshold value of the DC magnetic operation15 / 30 In
-
min/maxi threshold value of the DC thermal operation1.13 / 1.45 In
-
Rating current -10°C according to IEC 6094783.72 A
-
Rating current -15°C according to IEC 6094785.22 A
-
Rating current -20°C according to IEC 6094786.7 A
-
Rating current -25°C according to IEC 6094788.15 A
-
Rating current -5°C according to IEC 6094782.2 A
-
Rating current 0°C according to IEC 6094780.64 A
-
Rating current 10°C according to IEC 6094777.43 A
-
Rating current 15°C according to IEC 6094775.78 A
-
Rating current 20°C according to IEC 6094774.09 A
-
Rating current 25°C according to IEC 6094772.36 A
-
Rating current 30°C according to IEC 6094770.59 A
-
Rating current 35°C according to IEC 6094768.77 A
-
Rating current 40°C according to IEC 6094766.9 A
-
Rating current 45°C according to IEC 6094764.98 A
-
Rating current 5°C according to IEC 6094779.05 A
-
Rating current 50°C according to IEC 6094763 A
-
Rating current 55°C according to IEC 6094760.26 A
-
Rating current 60°C according to IEC 6094757.38 A
-
Rating current 65°C according to IEC 6094754.35 A
-
Rating current 70°C according to IEC 6094751.14 A
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-110 kA
-
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-110 kA
-
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-230 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-230 kA
-
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-215 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-215 kA
-
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-110 kA
-
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-110 kA
-
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-230 kA
-
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-215 kA
-
Rating current -25°C78.67 A
-
Rating current -20°C77.38 A
-
Rating current -15°C76.06 A
-
Rating current -10°C74.72 A
-
Rating current -5°C73.36 A
-
Rating current 0°C71.97 A
-
Rating current 5°C70.56 A
-
Rating current 10°C69.11 A
-
Rating current 25°C64.58 A
-
Rating current 30°C63 A
-
Rating current 35°C60.96 A
-
Rating current 40°C58.86 A
-
Rating current 45°C56.68 A
-
Rating current 50°C54.4 A
-
Rating current 55°C52.03 A
-
Rating current 60°C49.55 A
-
Rating current 65°C46.94 A
-
Rating current 70°C44.17 A
-
Correction factor of rating current for 2 devices placed side-by-side1
-
Correction factor of rating current for 3 devices placed side-by-side0.95
-
Correction factor of rating current for 4 and 5 devices placed side-by-side0.9
-
Correction factor of rating current for 6 devices placed side-by-side0.85
-
Correction factor of magnetic tripping with 100 Hz1.1
-
Correction factor of magnetic tripping with 200 Hz1.2
-
Correction factor of magnetic tripping with 400 Hz1.5
-
Correction factor of magnetic tripping with 60 Hz1.1
-
Depth of installed product70 mm
-
Height of installed product83 mm
-
Width of installed product52.5 mm
-
Frequency50 to 60 Hz
-
Maximum power loss per pole according to the product standard13 W
-
Total power loss under IN19.9 W
-
Power loss per pole at In7.12 W
-
Electric endurance in number of cycles4000
-
Number of mechanical operations20000
-
Type of top connection for modular deviceswith screw
-
Tightening torque2,8Nm
-
Type of top rail clip for modular devicesNA
-
Type of bottom rail clip for modular devicesplastic
-
Type of Bottom Connection for modular devicesBIconnect
-
Top removability for modular devicesYes
-
Bottom removability for modular devicesYes
-
Suitable for flush-mountingYes
-
Connection cross-section at output with screw, for flexible conductor1 / 25 mm²
-
Connection cross-section at output with screw, for massive conductor1 / 35 mm²
-
Connection cross-section for rigid conductor, upstream terminals with screws1 / 35 mm²
-
Connection cross-section of the access with screws, with flexible conductor1 / 25 mm²
-
Downstream cage clamp delivery statusopened
-
Upstream cage clamp delivery statusopened
-
Can be accessorizedYes
-
Standard textEN 60898-1 ; IEC 60947-2
-
REACH conformNo
-
RoHS conformYes
-
Halogen freeNo
-
Operating temperature-25…70 °C
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Altitude2000 m
-
Storage/transport temperature-25…80 °C
-
Temperature of calibration50 °C
Downloads
-
Product image
-
ProductDataSheet
Product data sheets for NDN363A
UK_PD_TDS_TransformerMotorprotection.pdf
PDF204 KB -
ProductLicence
Product licence for NDN363A
Licence for UNITED_KINGDOM
PDF243 KBProduct licence for NDN363A
Licence for ITALY
PDF519 KB -
ProductECDeclaration
EU Declaration of conformity for NDN363A
Declaration
PDF710 KBEU Declaration of conformity for NDN363A
EU Declaration of Conformity
PDF650 KBEU Declaration of conformity for NDN363A
Declaration
PDF689 KBEU Declaration of conformity for NDN363A
UKCA Declaration of Conformity
PDF653 KBEU Declaration of conformity for NDN363A
Declaration
PDF786 KBEU Declaration of conformity for NDN363A
Declaration
PDF716 KB -
ProductEnvironmentProfile
Product environmental profile for NDN363A
PEP - MCB 1P 6kA B-16A, 1 module (english)
PDF9 MBProduct environmental profile for NDN363A
PDF432 KB -
ProductROHS
Pollutant guidelines for NDN363A
RoHS declaration NDN363A (english)