KNX room cont., colourdisplay, intg bus coupling unit, KNX 80660100
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
-
Easy link functionsswitching of scenes (1..8) possible ; operating mode heating, cooling or heating/cooling can be selected ; switching PI-control (PWM) or switching 2-point control can be selected ; heating type warm water heating, warm water underfloor heating, electric heating, electric underfloor heating or split unit can be selected ; cooling type cooling ceiling, convector fan or split unit can be selected ; comfort, standby, night-time reduction, frost/heat protection operating mode switchable via scene ; push-button functions: including switching, dimming, roller shutter/blind, timer, priority, operating mode changeover
-
Functionwith keylock ; with holiday switching ; with frost protection function ; for switch, dimmer and shutter functions ; deactivate automatic function
-
Functionoperating modes heating, cooling, heating/cooling or background heating and additional heating/cooling can be selected ; control modes switching PI-control (PWM), continuous PI control or switching 2-point control can be selected ; heating types warm water heating, warm water underfloor heating, electric heating, electric underfloor heating, split unit or adjustable via object ; Push-button functions for switching, dimming, roller shutter/blind, value transmitter 1 and 2 byte, thermostat, scene, priority
-
OperationOperation via sensitive Touch control surface
-
Indication / displaydisplay of set or actual temperature ; Screen saver ; LC display with symbol display ; Time and date display ; to display and initiate actions
-
Auxiliary voltage24 V DC
-
Operating voltage over bus21…32 V DC
-
Current consumption (operation)25 mA
-
Bus current consumption (data transfer)max. 10 mA
-
Insertion depth32 mm
-
Dimensions of display (W x H)38.28 x 30.26 mm
-
Width of rail mounted device (RMD)0 modules
-
Width71 mm
-
TFT screen size1.93 ″
-
Installation modewith spreader claws ; for flush-mounted and hollow-wall mounting ; for single mounting ; for vertical mounting
-
Bus coupling unitwith integral bus coupling unit
-
Bus connectionbus connection via connecting terminal
-
Connectionwith additional connection for external floor temperature sensor/remote sensor
-
Supported configuration modessystem, easy
-
Timewith automatic summer/winter time change-over
-
Heatingfor heating and/or cooling mode ; heating or cooling possible in 2 stages
-
Controlfor individual single room temperature control ; control parameter for heating / cooling unit pre-set
-
Differentiation characteristic 2 - Saleswith colour display
-
Differentiation characteristic 3 - Salesintegrated bus coupling unit
-
REACH conformNo
-
Halogen freeNo
-
Operating temperature-5…45 °C
-
Storage/transport temperature-20…70 °C (storage at > 45°C reduces the service life)
-
Temperaturecomfort, standard and night temperature ; temperature measurement via internal and/or connectable temperature sensor with average determination ; additional connection for external temperature sensor
-
Energy efficiency classIV (2%)
-
Application, usageKNX - operating systems
-
Product familyProduct family: heating, ventilation, air conditioning
-
Compositionbasis element
-
Main design lineKNX
-
Information textThe KNX room controller in comparison with the thermostat also has push-button functions and can thus control all subsystems in a room.
Downloads
-
Product image
-
ProductNotice
Instruction manuals for 80660100
PDF2 MBInstruction manuals for 80660100
PDF4 MB -
ProductETSBase
Product-Database ETS for 80660100
ETS Database for 80XX0100
KNXPROD577 KBProduct-Database ETS for 80660100
ETS4 (vers. 1.0) - KNX Database for KNX Thermostat/room-controller
KNXPROD574 KB -
ProductApplicationDescription
Application guides ETS / easy link for 80660100
Application description EASY for 80440100-80660100 - KNX room thermostat/room controller (EN, 2020-09), easy link
PDF2 MBApplication guides ETS / easy link for 80660100
Application description EASY for 80440100-80660100 - KNX room thermostat/room controller (EN, 2020-09), easy link
PDF2 MBApplication guides ETS / easy link for 80660100
Application description ETS for 80440100-80660100 - KNX thermostat/room controller (EN, 2021-12)
PDF11 MB -
ProductECDeclaration
EU Declaration of conformity for 80660100
Declaration of Conformity
PDF900 KBEU Declaration of conformity for 80660100
EU Declaration of Conformity
PDF317 KBEU Declaration of conformity for 80660100
Declaration of Conformity
PDF900 KB -
ProductEnvironmentProfile
Product environmental profile for 80660100
PDF202 KB -
ProductROHS
Pollutant guidelines for 80660100
RoHS-declaration 2023-10-20 (english)
PDF33 KBPollutant guidelines for 80660100
REACH-declaration 2023-10-20 (english)
PDF33 KB