MCB 3P 6kA C-10A 3M MCN310
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
-
Number of protected poles3
-
Number of poles3 P
-
Type of pole3 P
-
CurveC
-
Concurrently switching N-neutralNo
-
Number of modules3
-
Top connection alignement for modular devicesAligned terminal
-
Bottom connection alignement for modular devicesAligned terminal
-
Rated short circuit breaking capacity Icn AC according IEC60898-16 kA
-
Rated operational voltage Ue230 / 400 V
-
Type of supply voltageAC
-
Frequency50/60 Hz
-
Rated insulation voltage500 V
-
Rated impulse withstand voltage4000 V
-
Rated current10 A
-
Rated service breaking capacity Ics AC according IEC 60898-16 kA
-
min/maxi threshold value of the AC thermal operation1.13 / 1.45 In
-
Magnetic regulating currrent5 / 10 In
-
min/maxi threshold value of the DC magnetic operation7 / 15 In
-
min/maxi threshold value of the DC thermal operation1.13 / 1.45 In
-
Breaking capacity on 1 pole for IT 400V NF 60947-23 kA
-
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-16 kA
-
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-210 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-210 kA
-
Rating current -25°C13.3 A
-
Rating current -20°C13.1 A
-
Rating current -15°C12.8 A
-
Rating current -10°C12.5 A
-
Rating current -5°C12.2 A
-
Rating current 0°C11.9 A
-
Rating current 5°C11.6 A
-
Rating current 10°C11.3 A
-
Rating current 15°C11 A
-
Rating current 20°C10.7 A
-
Rating current 25°C10.4 A
-
Rating current 30°C10 A
-
Rating current 35°C9.6 A
-
Rating current 40°C9.3 A
-
Rating current 45°C8.9 A
-
Rating current 50°C8.4 A
-
Rating current 55°C8 A
-
Rating current 60°C7.5 A
-
Rating current 65°C7 A
-
Rating current 70°C6.5 A
-
Correction factor of rating current for 2 devices placed side-by-side1
-
Correction factor of rating current for 3 devices placed side-by-side0.95
-
Correction factor of rating current for 4 and 5 devices placed side-by-side0.9
-
Correction factor of rating current for 6 devices placed side-by-side0.85
-
Correction factor of magnetic tripping with 100 Hz1.1
-
Correction factor of magnetic tripping with 200 Hz1.2
-
Correction factor of magnetic tripping with 400 Hz1.5
-
Correction factor of magnetic tripping with 60 Hz1
-
Depth of installed product70 mm
-
Height of installed product83 mm
-
Width of installed product52.5 mm
-
Frequency50 to 60 Hz
-
Total power loss under IN5.8 W
-
Power loss per pole at In2 W
-
Electric endurance in number of cycles4000
-
Number of mechanical operations20000
-
Type of top connection for modular deviceswith screw
-
Tightening torque2,8Nm
-
Type of Bottom Connection for modular devicesBIconnect
-
Connection cross-sect. flexible conductor1 / 25mm²
-
Connection cross-sect. rigid cable1 / 35mm²
-
Connection cross-section of input and output with screws, for massive conductors1 / 35 mm²
-
Connection cross section of access and exit with screws, for flexible conductor1 / 25 mm²
-
Type of connectionwith screw
-
Standard textEN 60898-1
-
REACH conformNo
-
RoHS conformYes
-
Halogen freeNo
-
Operating temperature-25…70 °C
-
Degree of pollution according to IEC 60664 / IEC 60947-22
-
Class of energy limitation I²t3
-
Altitude2000 m
-
Air humidity protectionfor all climates
-
Storage/transport temperature-25…80 °C
Downloads
-
Images
Images may be subject to copyright
Product Image MCN310
-
ProductECDeclaration
EU Declaration of conformity for MCN310
ULCA Declaration of Conformity
PDF541 KBEU Declaration of conformity for MCN310
EU Declaration of Conformity
PDF537 KBEU Declaration of conformity for MCN310
MCB
PDF716 KBEU Declaration of conformity for MCN310
Declaration
PDF410 KBEU Declaration of conformity for MCN310
Declaration
PDF753 KBEU Declaration of conformity for MCN310
MCB
PDF773 KBEU Declaration of conformity for MCN310
Declaration
PDF468 KBEU Declaration of conformity for MCN310
Declaration
PDF305 KBEU Declaration of conformity for MCN310
Declaration
PDF535 KB -
ProductEnvironmentProfile
Product environmental profile for MCN310
PEP_Hager_MCN116_EN_1772013
PDF365 KBProduct environmental profile for MCN310
PDF377 KB -
ProductROHS
Pollutant guidelines for MCN310
REACH-declaration 2023-10-20 (english)
PDF33 KBPollutant guidelines for MCN310
RoHS-declaration 2023-10-20 (english)
PDF32 KB
-
To have the REACH certificate for this product,
please contact us here, and precise the product reference: environmentaldata.europe@hagergroup.com