Moulded Case Circuit Breaker h630 3P 70kA 630A LSI HED630H
EAN-Nr.
3250613349615
Packaging
1 piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Stop delivery w sub Example text: This product is now obsolete. However, you can view the following products as replacements or extensions. As the functions of the replacement product are not absolutely identical, please consult your nearest Hager partner if you have any questions.
Complete your system
Optional accessories
-
Connection Functions 1 products available -
Shunt release 5 products available -
Auxiliaries contact block 2 products available -
Terminal cover 1 products available -
Padlock barrier for switch 1 products available
Complete your system
Technical characteristics
Electric current
-
Rated current630 A
-
Rated ultimate short-circuit breaking capacity Icu under 230 V AC IEC 60947-2100 kA
-
Rated ultimate short-circuit breaking capacity Icu under 240 V AC IEC 60947-2100 kA
-
Rated ultimate short-circuit breaking capacity Icu under 400 V AC IEC 60947-270 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415 V AC IEC 60947-270 kA
-
Breaking capacity on 1-pole for AC 230 V IEC 60947-260 kA
-
Breaking capacity on 1-pole for AC 400 V IEC 60947-29 kA
Architecture
-
Number of poles3
-
Control/operation elementToggle
-
Device construction typeFixed built-in
Capacity
-
Number of modules8
Tripping
-
Response time when opening10 ms
Settings
-
Magnetic protection knob setting xIN2.5, 5, 8
-
Range of magnetic adjustment3500 A, 4410 A, 5600 A, 6300 A, 6300 A, 6300 A, 6300 A, 6300 A
-
Thermal protection knob setting xIN0.4, 0.5, 0.63, 0.8, 0.9, 0.95, 1
-
Adjustment range short-term delayed short-circuit release0 - 0 A
Frequency
-
Frequency50 - 60 Hz
Installation, mounting
-
Nominal tightening torque22 - 22 Nm
-
Mounting-/Connection PositionFront
Voltage
-
Rated impulse withstand voltage Uimp8000 V
-
Rated insulation voltage Ui800 V
-
Rated operational voltage Ue220 - 690 V
Functions
-
Trip unitLSI
Main electrical attributes
-
Magnetic protection trip time100 - 200 ms
Power
-
Total power loss under IN120 W
-
Power loss per pole at In40 W
Endurance
-
Electric endurance in number of cycles1000
-
Number of mechanical operations4000
Equipment
-
Number of auxiliary contacts as change-over contact0
-
Number of auxiliary contacts as normally closed contact0
-
Number of auxiliary contacts as normally open contact0
Safety
-
Ingress Protection (IP) classIP4X
Use conditions
-
Operating temperature-25 - 70 °C
Connection
-
Cross-section flexible conductor35 - 240 mm²
-
Cross-section rigid conductor35 - 240 mm²
-
Connector/plug typeTerminal
Controls and indicators
-
Motor drive integratedNo
Compatibility
-
Suitable for DIN RailNo
Power supply
-
Position power supplyBidirectional
Environmental value
We are committed to bettering our environmental performance by reducing our footprint while acting as a sustainability enabler for our customers. Learn More
Certifications and documents
Downloads
More documentation