Output module 4x 16A /230V~, KNX TYA604C
EAN
3250616059849
Packaging
1 Piece
Login to create a product list
You need to be logged into your myHager account to create product lists
Technical properties
Architecture
-
Bus systemyes
Functions
-
Multi-phase modesuitable to switch different external conductors
-
Functionwith positioning function for blind and lamella position ; with safety functions e.g. for wind, rain, alarm ; with sun shade function
-
SwitchingFor switching, e.g. of 4 independent loads or activation of 2 drives
-
Operating modeany combined operation from drive and switching functions possible
Configuration
-
Number of modules4
Controls and indicators
-
Indicator lampyes
-
OperationManual operation can be activated via selection switch, thereby deactivation of the KNX function ; manual operation per channel using button (single-area operation)
-
Indication / displaystatus LED integrated in the manual operation button
-
Manual selection switches / push-buttonsmanual operation buttons for on/off (up/down) and bus function on/off per channel/device
-
Button / push-buttonwith illuminated programming button
Main electrical features
-
Rated current16 A
Voltage
-
Operating voltage over bus21…32 V DC
-
Output voltage230 V~
-
System supply voltage30V DC via bus
Electric current
-
Bus current consumption (data transfer)4 mA
-
Bus current consumption (idle)3 mA
-
Number of entry circuits0
-
Maximum through current16 A
-
Switching current at cos φ = 0.8max. 16 A
Dimensions
-
Depth65 mm
-
Width of rail mounted device (RMD)4 modules
-
Height90 mm
Power
-
Total power loss under IN8 W
-
Output power2300 W
-
Conventional transformers1600 VA
-
Electronic transformers1200 W
Lighting control
-
Fluorescent lamps with electronical ballast (EB)20 x 36 W
-
- uncompensated1200 VA
Fluorescent bulbs control
-
Energy-saving lamps18 x 23 W
-
Power lighting fluo lamps18x23W
-
Max. power fluo. duo lamp comp. series20 x 36 W
LED control
-
Max number of LED/CFL lamps18
-
230V LED lamps18 x 23 W
-
Power LED216 W
-
LEDStatus LED integrated in manual operation button
Incandescent bulbs control
-
Max. power with incandescent lamps2300 W
-
230 V incandescent lamps2300 W
-
230 V halogen lamps2300 W
-
230 V incandescent lamps and halogen lamps2300 W
Connection
-
Connection cross-sect. flexible conductor0,75 / 2,5mm²
-
Connection cross-sect. rigid cable0,75 / 2.5mm²
-
Conductor cross-section (flexible)0.75…2.5 mm²
-
Conductor cross-section (rigid)0.75…2.5 mm²
-
Type of contacts4NO
-
Bus coupling unitwith integral bus coupling unit
-
Type of connectionwith QuickConnect plug-in terminals
-
Bus connectionbus connection via connecting terminal
Settings
-
Supported configuration modessystem
-
Settingswitching time on change of direction adjustable
Scope of delivery
-
Bus connection includedYes
Equipment
-
Modular expandabilityNo
-
Potential-freewith potential-free NO contacts as well as NC contact parameterisable
Use
-
Differentiation characteristic 3 - Saleswith plug-in terminals
Safety
-
REACH conformNo
-
RoHS conformYes
-
Halogen freeNo
Use conditions
-
Operating temperature-5…45 °C
-
Storage/transport temperature-20…70 °C
Identification
-
Main design lineKNX
Downloads
-
Product image
-
ProductNotice
Instruction manuals for TYA604C
PDF1 MB -
ProductETSBase
Logiciel d'application ETS du TYA604A_B_C_D
VD51000 KBLogiciel d'application ETS du TYA604A_B_C_D
KNXPROD487 KB -
ProductApplicationDescription
Application description ETS TYA604ABCD_TYB606ABCD_TYA608ABCD_TYA610ABCD_TYM616D_TYM620D_TYB602F
PDF10 MB -
ProductECDeclaration
EU Declaration of conformity for TYA604C
PDF303 KB -
ProductEnvironmentProfile
Product environmental profile for TYA604C
PDF307 KBProduct environmental profile for TYA604C
PDF398 KB -
ProductROHS
REACH-declaration 2023-10-20 (english)
PDF33 KBRoHS-declaration 2023-10-20 (english)
PDF33 KB
More documentation