Safety and compliance

Discover how our products meet both international and local safety standards, and why Singapore’s SAFETY Mark certification plays a vital role in ensuring consumer protection and regulatory compliance.

Standards

IEC Standard / SS Standard / BS Standard

Our product ranges fully comply with international and local standards. These include:

 Comprehensive third-party laboratory testing

• Certified test reports and documentation available (e.g., CB Scheme)
• Certificates renewable in accordance with local regulatory requirements


For access to specific test reports and certificates, please don’t hesitate to contact us directly


Learn more

IEC 60898 vs. IEC 60947

villawestling_promo-push_731x392px

IEC 60998

IEC 60898-1 relates to low-voltage circuit breakers for use in household and similar installations viz., miniature circuit breakers (MCBs).

 

 

Domestic applications: households, retail spaces, schools, offices…

 

 

 

IEC 60947

IEC 60947-2 relates to low voltage circuit breakers for use in industrial and similar installations viz., miniature circuit breakers (MCBs) moulded case circuit breakers (MCCBs) or air circuit breakers (ACBs).

 

Industrial applications: car assembly, petrochemical plants, steel manufacturing… + commercial installations.

 

Safety mark

 

The SAFETY Mark is a certification issued by the Consumer Product Safety Office (CPSO) that signifies compliance with Singapore’s safety regulations. Controlled Goods must be registered and labeled with this mark before they can be distributed locally. Registered Suppliers are responsible for proper labeling, and CPSO may conduct spot-checks at warehouses when necessary.

This scheme is regulated by Enterprise Singapore (ESG), the official body for standards and accreditation in Singapore.

 

Currently, 33 categories of household electrical, electronic, and gas appliances and accessories are designated as Controlled Goods. These require a Certificate of Conformity (CoC) and must carry the SAFETY Mark.

Learn more

SAFETY Mark for Hager products

All Hager products that belong to SAFETY Mark Controlled Goods are appropriately marked in accordance with these guidelines, including:

Wiring Accessories (WA)
Residual Current Circuit Breakers (RCCBs)

 

Each SAFETY Mark includes an 8-digit certification number (format: XXYYYY-ZZ), issued by accredited Certification Bodies (CABs), which links the product to its Registered Supplier and classification.
 
To ensure safety and peace of mind, always choose products that carry the SAFETY Mark prominently*.

 

*Details about SAFETY Mark certification can be verified through the Consumer Product Safety Office website. More comprehensive regulatory information can be found in the Singapore Consumer Protection Regulation Info Booklet.

Residual Current Circuit Breaker

SS97:2016

Switches

IEC60669-1:2017 (Ed.4.0)

13A Switched Socket Outlets

SS145-2:2018

  • Domestic electric wall switch Standards
     

    Domestic electric wall switches, which are electrical manually operated general purpose switches for alternating current only, with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A, intended for household fixed-electrical installations.

     

     13A fused connection units (switched)  SS 145-4: 2022
     General purpose domestic electric wall switch  IEC 60669-1: 2017 (Ed. 4.0)

  • Mains socket-outlets Standards 

     

    Mains socket-outlets, which are electrical devices that have 13-amp or 15-amp switched shuttered socket-outlets in a single or multiple arrangement, to engage with the pins of a corresponding plug designed for flush mounting in a suitable box or for surface or panel mounting. 

     

     3-pin 13-amp socket-outlet SS 145-2:2018
     3-pin 13-amp socket-outlet (cooker control unit) BS 4177:1992 + A1:1993 + A2:1997 + A3:2004 + A4:2007
     3-pin 13-amp socket-outlet with RCD BS 7288:2016
     3-pin round type 15-amp socket-outlet SS 472:1999(2020) + E1:2001/A1:2020

  • Residual Current Circuit Breaker Standards 

     

    Residual current circuit breaker (RCCB), which is an electrical device intended for household fixed-electrical installation with sensitivity of 30 mA intended to protect persons against indirect contact, the exposed conductive parts of the installation being connected to an appropriate.

     

    Minimum Editions of Safety Standard(s) and Additional Requirements
     Current   From June 2024/2025*
     SS 97-1:2005  SS 97:2016

     

    *Effective from 1st June 2024 for new registrations, and 1st June 2025 for renewals of registrations, unless otherwise stated


  • IEC 60898 vs IEC 60947
     

     

     


    IEC 60898-1
    Domestic application
    IEC 60947-2
    Industrial application
    Max voltage  440V (AC)  1000V AC or 1500 DC
    Max current  125A up to 6300A
    Max breaking capacity  25kA  up to 150kA
    Type of CBs MCB  MCB, MCCB, ACB
     
    Pollution level 2  3
    Non tripping current  1.13 ln  1.05 ln
    Tripping current  1.45 ln  1.3 ln
    Ambient temperature  30° C  40° C