Safety and compliance
Standards
IEC Standard / SS Standard / BS Standard
Our product ranges fully comply with international and local standards. These include:
• Comprehensive third-party laboratory testing
• Certified test reports and documentation available (e.g., CB Scheme)
• Certificates renewable in accordance with local regulatory requirements
For access to specific test reports and certificates, please don’t hesitate to contact us directly

IEC 60898 vs. IEC 60947
Safety mark
The SAFETY Mark is a certification issued by the Consumer Product Safety
Office (CPSO) that signifies compliance with Singapore’s safety regulations.
Controlled Goods must be registered and labeled with this mark before they can
be distributed locally. Registered Suppliers are responsible for proper
labeling, and CPSO may conduct spot-checks at warehouses when necessary.
This scheme is regulated by Enterprise Singapore (ESG), the official body for standards and accreditation in Singapore.
Currently, 33 categories of household electrical, electronic, and gas appliances and accessories are designated as Controlled Goods. These require a Certificate of Conformity (CoC) and must carry the SAFETY Mark.

SAFETY Mark for Hager products
All Hager products that belong to SAFETY Mark Controlled Goods are appropriately marked in accordance with these guidelines, including:
• Wiring Accessories (WA)
• Residual Current Circuit Breakers (RCCBs)
Each SAFETY Mark includes an 8-digit certification number (format: XXYYYY-ZZ), issued by accredited Certification Bodies (CABs), which links the product to its Registered Supplier and classification.
To ensure safety and peace of mind, always choose products that carry the SAFETY Mark prominently*.
*Details about SAFETY Mark certification can be verified through the Consumer Product Safety Office website. More comprehensive regulatory information can be found in the Singapore Consumer Protection Regulation Info Booklet.
-
Domestic electric wall switch Standards
Domestic electric wall switches, which are electrical manually operated general purpose switches for alternating current only, with a rated voltage not exceeding 440 V and a rated current not exceeding 63 A, intended for household fixed-electrical installations.
13A fused connection units (switched) SS 145-4: 2022 General purpose domestic electric wall switch IEC 60669-1: 2017 (Ed. 4.0)
-
Mains socket-outlets Standards
Mains socket-outlets, which are electrical devices that have 13-amp or 15-amp switched shuttered socket-outlets in a single or multiple arrangement, to engage with the pins of a corresponding plug designed for flush mounting in a suitable box or for surface or panel mounting.
3-pin 13-amp socket-outlet SS 145-2:2018 3-pin 13-amp socket-outlet (cooker control unit) BS 4177:1992 + A1:1993 + A2:1997 + A3:2004 + A4:2007 3-pin 13-amp socket-outlet with RCD BS 7288:2016 3-pin round type 15-amp socket-outlet SS 472:1999(2020) + E1:2001/A1:2020
-
Residual Current Circuit Breaker Standards
Residual current circuit breaker (RCCB), which is an electrical device intended for household fixed-electrical installation with sensitivity of 30 mA intended to protect persons against indirect contact, the exposed conductive parts of the installation being connected to an appropriate.
Minimum Editions of Safety Standard(s) and Additional Requirements Current From June 2024/2025* SS 97-1:2005 SS 97:2016 *Effective from 1st June 2024 for new registrations, and 1st June 2025 for renewals of registrations, unless otherwise stated
-
IEC 60898 vs IEC 60947
IEC 60898-1
Domestic applicationIEC 60947-2
Industrial applicationMax voltage 440V (AC) 1000V AC or 1500 DC Max current 125A up to 6300A Max breaking capacity 25kA up to 150kA Type of CBs MCB MCB, MCCB, ACB
Pollution level 2 3 Non tripping current 1.13 ln 1.05 ln Tripping current 1.45 ln 1.3 ln Ambient temperature 30° C 40° C