Safety and compliance
Discover how our
products meet both international and local safety standards, and why Malaysia SIRIM
LABEL and ST-COA certification plays a vital role in ensuring consumer
protection and regulatory compliance.
Standards
IEC Standard / SS Standard / BS Standard
Our product ranges fully comply with international and local standards. These include:
• Comprehensive third-party laboratory testing
• Certified test reports and documentation available (e.g., CB Scheme)
• Certificates renewable in accordance with local regulatory requirements
For access to specific test reports and certificates, please don’t hesitate to contact us directly

IEC 60898 vs. IEC 60947
SIRIM mark
The SIRIM Mark is a certification issued by the SIRIM QAS International Sdn Bhd. After receiving the ST-COA from Energy Commission Malaysia, all controlled Items must be registered and labelled with this mark before they can be distributed locally. Registered Suppliers are responsible for proper labelling, and factory audit will be done annually to make sure all the products manufactured follow the standard requirement.
This scheme is regulated by SIRIM QAS International Sdn Bhd, the leading testing, inspection, and certification body in Malaysia.
Currently, 34 categories of household electrical and electronic appliances and accessories are designated as Controlled Items. These require a ST-COA (Certificate of Approval) from Energy Commission Malaysia.

SIRIM Mark for Hager products
All Hager products that belong to SIRIM Mark Controlled Items are appropriately marked in accordance with these guidelines, including:
• Wiring Accessories (WA)
• Miniature Circuit Breaker (MCB)
• Residual Current Circuit Breakers (RCCBs)
Each SIRIM Mark includes an individual QR code identity, issued by SIRIM QAS International Sdn Bhd, which links the product to the SIRIM database.
To ensure safety and peace of mind, always choose products that carry the SIRIM Mark prominently*.
*Details about SIRIM Mark certification can be verified through the SIRIM QAS International Sdn Bhd website. More comprehensive regulatory information can be found in the Guidelines For The Approval Of The Electrical Equipment Booklet (2024 Edition).
-
Switched & Un-switched Socket Outlet Standards
• for fixing at a point at which fixed wiring terminates;
• provides a detachable connection with the pins of a plug;
• has two or more contacts;Detail of Equipment National Standard International Standard 13A Switch & unswitch socket outlet MS 589-2:2018 BS 1363- 2:2016+A1:2018 15A socket outlet & Plug MS 1577:2003 No corresponding international standard
-
• for fixing at a point at which fixed wiring terminates;
• provides a detachable connection with the pins of a plug;
• has two or more contacts;Detail of Equipment National Standard International Standard 13A Switch & unswitch socket outlet MS 589-2:2018 BS 1363- 2:2016+A1:2018 15A socket outlet & Plug MS 1577:2003
No corresponding international standard
• for fixing at a point at which fixed wiring terminates;
• provides a detachable connection with the pins of a plug;
• has two or more contacts;National Standard International Standard MS IEC 60898-1: 2007
IEC 60898-1: 2003
-
Switch and Dimmer Standards
• an air-break switch;
• for connection to the wiring of an electric installation;
• primarily for mounting on a vertical surface;
• manually opened and manually closed; and
• has a rating up to 63A.
Detail of Equipment National Standard International Standard General Purpose Switch MS IEC 60669- 1:2017 IEC 60669-1:2017 Electronic Switch MS IEC 60669-1: 2017
MS IEC 60669-2-1: 2012IEC 60669-1:2017
IEC 60669-2-1:2009Isolator Switch MS IEC 60947- 1:2010
MS IEC 60947- 3:2010IEC 60947-1:2007
IEC 60947-3:2008
-
Miniature Circuit Breaker (MCB) Standard
• an enclosed air break switch;
• opens a low voltage circuit automatically under pre-determined conditions of over-current;
• has a nominal rating not exceeding 125 A and has a current breaking capacity of up to 10kA.
• fusion of one or more of its specially designed and proportioned components, opens the circuit in which it is inserted and breaks the current when this exceeds a given value for a sufficient time. The fuse comprises all the parts that form the complete device.National Standard International Standard MS IEC 60898-1: 2007
IEC 60898-1: 2003
Residual Current Circuit Breaker (RCCB) Standards
• Isolates or initiates a tripping signal to isolate a low voltage supply to protected circuits, socket-outlets or equipment in the event of a current flow to earth which exceeds a pre-determined level;• has a rated residual current less than 300mA for devices intended for connection to fixed wiring or 10mA for other devices; and
• has a rated load current not exceeding 125 A for devices intended for connection of fixed wiring or 20 A for other devices.but does not include:
• a device intended to be used with a particular circuit-breaker other than a miniature overcurrent circuit breaker; or
• a device intended to protect an electricity supply authority distribution system.National Standard International Standard MS IEC 61008-1: 2012
MS IEC 61008-2-1: 2003
or
MS IEC 61008-1: 2012
MS IEC 61008-2-2: 2003
IEC 61008-1: 2010
IEC 61008-2-1: 1990
or
IEC 61008-1: 2010
IEC 61008-2-2: 1990
-
IEC 60898 vs IEC 60947
IEC 60898-1
Domestic applicationIEC 60947-2
Industrial applicationMax voltage 440V (AC) 1000V AC or 1500 DC Max current 125A up to 6300A Max breaking capacity 25kA up to 150kA Type of CBs MCB MCB, MCCB, ACB
Pollution level 2 3 Non tripping current 1.13 ln 1.05 ln Tripping current 1.45 ln 1.3 ln Ambient temperature 30° C 40° C