Service Temporarily Unavailable

The server is temporarily unable to service your request due to maintenance downtime or capacity problems. Please try again later.

MCCB h630 3P 70kA 630A LSI • HED630H | Hager
EAN-Nr.
3250613349615
Packaging
1 piece

Moulded Case Circuit Breaker h630 3P 70kA 630A LSI HED630H

Complete your system

Optional accessories

  • Shunt release 1 products available

Technical characteristics

Elec­tric current
  • Rated current
    630 A
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 230 V AC IEC 60947-2
    100 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 240 V AC IEC 60947-2
    100 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 400 V AC IEC 60947-2
    70 kA
  • Rated ulti­mate short-­cir­cuit breaking capa­city Icu under 415 V AC IEC 60947-2
    70 kA
  • Breaking capa­city on 1-pole for AC 230 V IEC 60947-2
    60 kA
  • Breaking capa­city on 1-pole for AC 400 V IEC 60947-2
    9 kA
Archi­tec­ture
  • Number of poles
    3
  • Control/­op­er­a­tion element
    Toggle
  • Device construc­tion type
    Fixed built-in
Capa­city
  • Number of modules
    8
Trip­ping
  • Response time when opening
    10 ms
Settings
  • Magnetic protec­tion knob setting xIN
    2.5, 5, 8
  • Range of magnetic adjust­ment
    3500 A, 4410 A, 5600 A, 6300 A, 6300 A, 6300 A, 6300 A, 6300 A
  • Thermal protec­tion knob setting xIN
    0.4, 0.5, 0.63, 0.8, 0.9, 0.95, 1
  • Adjust­ment range short-term delayed short-­cir­cuit release
    0 - 0 A
Frequency
  • Frequency
    50 - 60 Hz
Install­a­tion, mounting
  • Nominal tight­ening torque
    22 - 22 Nm
  • Mount­ing-/­Con­nec­tion Posi­tion
    Front
Voltage
  • Rated impulse with­stand voltage Uimp
    8000 V
  • Rated insu­la­tion voltage Ui
    800 V
  • Rated oper­a­tional voltage Ue
    220 - 690 V
Func­tions
  • Trip unit
    LSI
Main elec­trical attrib­utes
  • Magnetic protec­tion trip time
    100 - 200 ms
Power
  • Total power loss under IN
    120 W
  • Power loss per pole at In
    40 W
Endur­ance
  • Elec­tric endur­ance in number of cycles
    1000
  • Number of mech­an­ical oper­a­tions
    4000
Equip­ment
  • Number of auxil­iary contacts as change-over contact
    0
  • Number of auxil­iary contacts as normally closed contact
    0
  • Number of auxil­iary contacts as normally open contact
    0
Safety
  • Ingress Protec­tion (IP) class
    IP4X
Use condi­tions
  • Oper­ating temper­ature
    -25 - 70 °C
Connec­tion
  • Cross-sec­tion flex­ible conductor
    35 - 240 mm²
  • Cross-sec­tion rigid conductor
    35 - 240 mm²
  • Connect­or/plug type
    Terminal
Controls and indic­ators
  • Motor drive integ­rated
    No
Compat­ib­ility
  • Suit­able for DIN Rail
    No
Power supply
  • Posi­tion power supply
    Bidirec­tional