HR510

EARTH LEAKAGE RELAY 0.03-10A TIME DELAY
EAN
3250613281311
Quantity
1
Trade price*
£382.20 /prt.*
More Information
Protection index IPIP30
Delay adjustableYes
Number of modules3
Altitude2000 m
Acceptable current rating with AC18 A
CE marking on labelAI2_B5_CE_01.JPG
Rated residual operating current30 / 100 / 300 / 500 / 1000 / 3000 / 10000 mA
Power consumed5 VA
Frequency50;60 Hz
Tightening torque1,7Nm
Maximum connection distance between receiver and transmitter25m and 50m twisted pair
Time delay of residual current0 / 0.1 / 0.3 / 0.4 / 0.5 / 1 / 3 s
Torroïds : Allowed overload30kA ; 100ms
Total power loss under IN4.1 W
Connection cross-sect. flexible conductor1 ; 2,5mm²
Residual current typeA
Rated operational voltage Ue230 V
Max operating voltage276 V
Earth leakage protection with toroidYes
Search wordsResidual current relay
Storage temperature-25/70 °C
Operating temperature-10/55 °C
Type of contactsStand 1 OF
European directive WEEEconcerned
Connection cross-section in massive cable for the measurement1.5/4 mm²
Connection cross-sect. rigid cable1,5 ; 4mm²
Connection cross-section in flexible cable for the measurement1/2.5 mm²
UnitPCE
Sales status3C
EAN3250613281311
See more features
Documentations
Instruction manuals for HR510 537 kbpdfDownload
Product data sheets for HR510 96 kbpdfDownload
Commercial Distribution Catalogue 13011 kbpdfDownload
More documentation

Share your latest install with the #HagerGang

Join the gang

Specifying Hager

We offer a range of product solutions for any project.
Find out how we can provide you with the ideal electrical solution for your next project.

Explore solutions

Catalogues & brochures

All product documentation and datasheets just one click away!

Explore
*Data is subject to errors and technical modifications. Prices are trade price, exclusive of VAT.